Plan Review Notes
Plan Review Notes For Permit 07120184
Permit Number 07120184
Review Stop M
Sequence Number 1
Notes
Date Text
2008-01-04 13:48:52REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENERGY CALCULATIONS: METHOD B FOR SHELL BUILDING HAS
 BEEN SUBMITTED WITH ASSUMPTIONS FOR FEATURES TO BE
 INSTALLED AT A LATER DATE. THESE ASSUMPTIONS (AND THE
 COMPLIANCE FORM) ARE MISSING HVAC EQUIPMENT. PLANS
 INDICATE THIS IS TO BE INSTALLED AT A LATER DATE AND
 SHALL BE INCLUDED IN THE ASSUMPTIONS AS WELL AS THE
 CALCULATIONS IN ACCORDANCE WITH FBC 13-101.1.6. THE
 SIZE OF HVAC EQUIPMENT SHOULD BE DETERMINED AT THIS
 TIME TO DEMONSTRATE RELATIVE ACCURACY OF ASSUMPTIONS
 BEING MADE. THIS SHALL BE DEMONSTRATED WITH COOLING
 LOAD CALCULATIONS IN ACCORDANCE WITH FBC
 13-407.1.ABC.1. PROVIDE MISSING INFORMATION AND
 RESUBMIT ENERGY CALCULATIONS WITH THIS INFORMATION
 INCLUDED.
  
 2. TOP OF PARAPET WALL IS SHOWN AT 21 FEET. WHERE
 EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE INSTALLED
 ONELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET,
 SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM
 GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES?
 LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH.
 FBC, M 306.5.
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 A. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES.
 B. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES ON CENTER.
 C. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES DEEP.
 D. THERE SHALL BE A MINIMUM OF 18 INCHES BETWEEN
 RAILS.
 E. RUNGS SHALL HAVE A MINIMUM 0.75-INCH DIAMETER AND BE
 CAPABLE OF WITHSTANDING A 300-POUND LOAD.
 F. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS.
  
 3. PROVIDE STRUCTURAL DETAIL FOR ATTACHMENT OF A/C ROOF
 CURBS TO BUILDING TO MEET WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBC, M 301.13. THE PROPOSED A/C
 EQUIPMENT LISTED ON PG ME1 MAY BE USED FOR THESE
 CALCULATIONS. SEE ALSO PG S-3 "SPECIALTY ENGINEERED
 PRODUCTS" NOTE 1(B). PROVIDE THE REQUESTED INFORMATION
 FOR BUILDING PLAN REVIEW.
  