Plan Review Notes
Plan Review Notes For Permit 07120184
Permit Number 07120184
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-01-04 19:10:31*****DENIED*****
  
 1.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.SHOW THE LOCATION OF THE NEAREST EXISTING AND/OR
 PROPOSED FIRE HYDRANT(S) TO THE NEW STRUCTURE.
  
 2.ON SHEET A1.0 IN THE DESIGN STANDARDS/APPLICABLE
 CODES, THERE SEEMS TO BE AN INTERMINGLE OF THE FIRE
 CODES. AMEND TO READ AS SUCH:FLORIDA FIRE PREVENTION
 CODE (2004 EDITION);NFPA 1, UNIFORM FIRE CODE, 2003
 EDITION
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY/DEVELOPMENT OR VICINITY THEREOF (INCLUDING
 STREETS, ALLEYS, FIRE LANES).
  
 5.ON THE APPROPRIATE EXTERIOR ELEVATION, SHOW/DISPLAY
 THE NUMERICAL ADDRESS FOR THIS STRUCTURE.THE ADDRESS
 NUMBERS SHALL BE AT LEAST 8" IN HEIGHT AND AT LEAST 1"
 IN STROKE/WIDTH.IF A MONUMENT SIGN IS USED OR WILL BE
 USED FOR MULTIPLE COMMERCIAL STRUCTURES IN THE
 DEVELOPMENT, THE ADDRESS RANGE FOR THE DEVELOPMENT
 SHALL BE POSTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722