| Plan Review Notes For Permit 07120184 |
| Permit Number |
07120184 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-04 19:10:31 | *****DENIED***** | | | | | | 1.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE | | | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.SHOW THE LOCATION OF THE NEAREST EXISTING AND/OR | | | PROPOSED FIRE HYDRANT(S) TO THE NEW STRUCTURE. | | | | | | 2.ON SHEET A1.0 IN THE DESIGN STANDARDS/APPLICABLE | | | CODES, THERE SEEMS TO BE AN INTERMINGLE OF THE FIRE | | | CODES. AMEND TO READ AS SUCH:FLORIDA FIRE PREVENTION | | | CODE (2004 EDITION);NFPA 1, UNIFORM FIRE CODE, 2003 | | | EDITION | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH EMERGENCY RESPONSE ACCESS TO THE | | | PROPERTY/DEVELOPMENT OR VICINITY THEREOF (INCLUDING | | | STREETS, ALLEYS, FIRE LANES). | | | | | | 5.ON THE APPROPRIATE EXTERIOR ELEVATION, SHOW/DISPLAY | | | THE NUMERICAL ADDRESS FOR THIS STRUCTURE.THE ADDRESS | | | NUMBERS SHALL BE AT LEAST 8" IN HEIGHT AND AT LEAST 1" | | | IN STROKE/WIDTH.IF A MONUMENT SIGN IS USED OR WILL BE | | | USED FOR MULTIPLE COMMERCIAL STRUCTURES IN THE | | | DEVELOPMENT, THE ADDRESS RANGE FOR THE DEVELOPMENT | | | SHALL BE POSTED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|