Plan Review Notes
Plan Review Notes For Permit 07120184
Permit Number 07120184
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-12 15:18:07** DENIED **
  
 ** APPLIED SHELL FOR STARBUCKS.
  
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL SHEETS CONTAIN
 THE RELEVANT CODES FOR DESIGN. PLEASE LIST THE
 FOLLOWING.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE BE SURE THE APPLIED ADDRESS AND
 LOCATION IS LISTED IN TITLE BLOCKS. APPLIED ADDRESS FOR
 THIS LOCATION IS 8150 OKEECHOBEE BLVD.
 FAC 61G15-23.002, FBC 106.5, 106.1.2
  
 3) NOTE: PLEASE CLARIFY APPLIED SHELL PERMIT AS THIS
 LIST THE OCCUPANT AS BEING *STARBUCKS* HOWEVER AS A
 SHELL THE TENANT MAY NOT BE KNOWN AT THIS TIME. IS THIS
 POSSIBLE FUTURE TENANT?
 PLEASE KNOW THAT IF ANY INTERIOR WORK COMMENCES BEFORE
 CO OF SHELL THIS WILL AFFECT THE ASSUMPTIONS IN THE
 ENERGY CALCULATIONS AS SUBMITTED AS WELL AS THE LOAD
 CALCULATIONS FOR KNOWN ELECTRICAL APPLIANCES FOR
 BUILDING.
 THIS COMMENT IS FOR CLARIFICATION AND INFORMATIONAL
 PURPOSE AT THIS TIME.
 FBC 106.1.2 ADDITIONAL INFORMATION AND COORDINATION.
  
 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED CONTAIN AN ADDENDUM TO THE CALCULATIONS.
 PLEASE KNOW THAT ANY CHANGES TO THE REPORT MUST BE
 INCLUDED IN THE FLA-COM PROGRAM.
 PLEASE BE SURE TO COORDINATE ALL ELECTRICAL LIGHTING ON
 PLANS WITH THAT OF THE LIGHTING IN THE INPUT DATA
 REPORTS.
 PLEASE SEE FOR EXAMPLE: EXTERIOR LIGHTING ON THE INPUT
 DATA REPORT SHOWS A TOTAL OF ONE LIGHT FIXTURE AT
 26WATTS. HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY
 SHOW AS MANY AS 5 EXTERIOR LIGHT FIXTURES AND THREE
 DIFFERENT TYPES OF FIXTURES?
  
 PLEASE BE SURE TO MAKE ADJUSTMENTS.
 THEINTERIOR LIGHTING ON THE IDR IS ASSUMPTIONS AT
 THIS TIME.
 13-415.2, 13-415.B.1
  
 5) NOTE: PLEASE BE SURE TO ADD NOTES ON PLANS FOR
 13-413.1.ABC.1.1 AND .2.2. (PART OF THIS SEEMS TO BE ON
 ME2 HOWEVER PART OF THE NOTE IS UNCLEAR)
  
 6) NOTE: PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 THE CERTIFICATION SHEETS ON THE ENERGY CALCULATIONS.
 PLEAS ALSO BE SURE THE ENGINEER SIGNS, DATES AND SEALS
 THE CERTIFICATION SHEET. (PAGE 3).
 13-103.1.1.1, FS 471.025
  
 7) NOTE: PLEASE CLARIFY LOCATIONS FOR A/C DISCONNECTS
 REQUIRED PER 440.11.
  
 8) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR THE APPLIED
 VALUE AS THE VALUE SEEMS LOW PER FBC 108.3.
 THE APPLIED VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COST, EVEN IF ANY OF THESE ITEMS ARE
 OWNER SUPPLIED.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES.
  
 9) NOTE: PLEASE CLARIFY WHERE SITE LIGHTING IS BEING
 FED FROM AND HOW THIS IS FIGURED INTO CALCULATIONS.
  
 10) NOTE: THIS NOTE ADDED. CLARIFY CONTINUOUS LOADS
 FIGURED AT 125% ALREADYOR TO BE ADJUSTED.
  
  
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  