| 2007-12-12 15:18:07 | ** DENIED ** |
| | |
| | ** APPLIED SHELL FOR STARBUCKS. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL SHEETS CONTAIN |
| | THE RELEVANT CODES FOR DESIGN. PLEASE LIST THE |
| | FOLLOWING. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE BE SURE THE APPLIED ADDRESS AND |
| | LOCATION IS LISTED IN TITLE BLOCKS. APPLIED ADDRESS FOR |
| | THIS LOCATION IS 8150 OKEECHOBEE BLVD. |
| | FAC 61G15-23.002, FBC 106.5, 106.1.2 |
| | |
| | 3) NOTE: PLEASE CLARIFY APPLIED SHELL PERMIT AS THIS |
| | LIST THE OCCUPANT AS BEING *STARBUCKS* HOWEVER AS A |
| | SHELL THE TENANT MAY NOT BE KNOWN AT THIS TIME. IS THIS |
| | POSSIBLE FUTURE TENANT? |
| | PLEASE KNOW THAT IF ANY INTERIOR WORK COMMENCES BEFORE |
| | CO OF SHELL THIS WILL AFFECT THE ASSUMPTIONS IN THE |
| | ENERGY CALCULATIONS AS SUBMITTED AS WELL AS THE LOAD |
| | CALCULATIONS FOR KNOWN ELECTRICAL APPLIANCES FOR |
| | BUILDING. |
| | THIS COMMENT IS FOR CLARIFICATION AND INFORMATIONAL |
| | PURPOSE AT THIS TIME. |
| | FBC 106.1.2 ADDITIONAL INFORMATION AND COORDINATION. |
| | |
| | 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED CONTAIN AN ADDENDUM TO THE CALCULATIONS. |
| | PLEASE KNOW THAT ANY CHANGES TO THE REPORT MUST BE |
| | INCLUDED IN THE FLA-COM PROGRAM. |
| | PLEASE BE SURE TO COORDINATE ALL ELECTRICAL LIGHTING ON |
| | PLANS WITH THAT OF THE LIGHTING IN THE INPUT DATA |
| | REPORTS. |
| | PLEASE SEE FOR EXAMPLE: EXTERIOR LIGHTING ON THE INPUT |
| | DATA REPORT SHOWS A TOTAL OF ONE LIGHT FIXTURE AT |
| | 26WATTS. HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY |
| | SHOW AS MANY AS 5 EXTERIOR LIGHT FIXTURES AND THREE |
| | DIFFERENT TYPES OF FIXTURES? |
| | |
| | PLEASE BE SURE TO MAKE ADJUSTMENTS. |
| | THEINTERIOR LIGHTING ON THE IDR IS ASSUMPTIONS AT |
| | THIS TIME. |
| | 13-415.2, 13-415.B.1 |
| | |
| | 5) NOTE: PLEASE BE SURE TO ADD NOTES ON PLANS FOR |
| | 13-413.1.ABC.1.1 AND .2.2. (PART OF THIS SEEMS TO BE ON |
| | ME2 HOWEVER PART OF THE NOTE IS UNCLEAR) |
| | |
| | 6) NOTE: PLEASE BE SURE THE OWNER AGENT IS SIGNED ON |
| | THE CERTIFICATION SHEETS ON THE ENERGY CALCULATIONS. |
| | PLEAS ALSO BE SURE THE ENGINEER SIGNS, DATES AND SEALS |
| | THE CERTIFICATION SHEET. (PAGE 3). |
| | 13-103.1.1.1, FS 471.025 |
| | |
| | 7) NOTE: PLEASE CLARIFY LOCATIONS FOR A/C DISCONNECTS |
| | REQUIRED PER 440.11. |
| | |
| | 8) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR THE APPLIED |
| | VALUE AS THE VALUE SEEMS LOW PER FBC 108.3. |
| | THE APPLIED VALUE IS TO INCLUDE ALL LABOR, MATERIALS, |
| | EQUIPMENT, DESIGN COST, EVEN IF ANY OF THESE ITEMS ARE |
| | OWNER SUPPLIED. |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES. |
| | |
| | 9) NOTE: PLEASE CLARIFY WHERE SITE LIGHTING IS BEING |
| | FED FROM AND HOW THIS IS FIGURED INTO CALCULATIONS. |
| | |
| | 10) NOTE: THIS NOTE ADDED. CLARIFY CONTINUOUS LOADS |
| | FIGURED AT 125% ALREADYOR TO BE ADJUSTED. |
| | |
| | |
| | |
| | ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |