| Date |
Text |
| 2008-02-21 11:59:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW COMMENTS |
| | WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | |
| | 1. **RESPONSE NOTED, HOWEVER WATER COOLERS ARE NOT |
| | COMPLIANT** |
| | SHEET A-3.0 PER TABLE 403.1.2 DRINKING FOUNTAINS ARE |
| | REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING |
| | FOUNTAIN. SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| | SECTION 11-4.15 AND ALL SUBSECTIONS. |
| | |
| | **PER FBC PLUMBING TABLE 403.1.2 WITH AN OCCUPANCY |
| | LOAD OF 146 PERSONS BEING INDICATED ON SHEET A-1.0, A |
| | MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED AND |
| | SHALL BE COMPLIANT WITH CHAPTER 11 FLORIDA |
| | ACCESSIBILITY CODE SECTION 11-4.15 AND ALL |
| | SUBSECTIONS. |
| | |
| | |
| | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| | INFORMATION) |
| | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| | MAXIMUM. |
| | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| | OF THE FRONT OF FOUNTAIN. |
| | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| | MOUNTED NEAR FRONT EDGE. |
| | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| | SPACE. |
| | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| | |
| | 2. **RESPONSE NOTED, HOWEVER SEE NOTE: BELOW PREVIOUS |
| | COMMENT** |
| | SHEET A-3.0 THE KITCHEN SINK SHALL BE ACCESSIBLE, |
| | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.24 AND ALL SUB SECTIONS. |
| | |
| | **NOTE: SHEET A-3.2 DETAIL 2, KITCHEN: PER CHAPTER 11 |
| | FLORIDA ACCESSIBILITY CODE PLEASE SHOW COMPLIANCE TO |
| | 11-4.24 SUBSECTIONS. |
| | |
| | **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE |
| | FOLLOWING INFORMATION) |
| | 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK.**CLEARLY INDICATE THAT CLEAR FLOOR SPACE SHALL |
| | EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK. 11-4.24.7 |
| | FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR ELECTRONICALLY |
| | CONTROLLED ARE ACCEPTABLE DESIGNS.**CLEARLY INDICATE |
| | FAUCET TYPE. |
| | |
| | 3. **OK** COMMENT ADDRESSED. |
| | |
| | 4. **OK** COMMENT ADDRESSED. |
| | |
| | 5. **COMMENT RESPONSE NOTED, HOWEVER SEE NOT: BELOW |
| | PREVIOUS COMMENT** |
| | SHEET P-1 SHOW THE LOCATION OF THE SANITARY BUILDING |
| | DRAIN AND THE WATER MAIN THAT THE KITCHEN SINK WILL BE |
| | CONNECTED TO. SECTION 106.1.2 ADDITIONAL DATA. |
| | |
| | **NOTE: SHEET P-1 IS INDICATING THE SANITARY WASTE, |
| | VENT AND POTABLE WATER TO THE SINK AS EXISTING (REMOVED |
| | SINK) HOWEVER THERE IS NO INDICATION ON THE DEMO PLAN |
| | SHEET A-2.0 THAT THERE WAS AN EXISTING SINK LOCATED IN |
| | THIS AREA. PLEASE CLARIFY THIS. PER CITY OF WPB |
| | AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS AND SECTION 106.1.2 ADDITIONAL |
| | DATA. |
| | |
| | **THE FOLLOWING IS A NEW COMMENT** |
| | |
| | 6. SHEETS A-1.0, A-3.0, A-3.1, A-3.2, A-4.0 AND A-5.0 |
| | ARE MISSING A DATE AT THE ARCHITECTS SIGNATURE AND SEAL |
| | AS WELL AS THE PRINTED NAME AND LICENSE NUMBER OF THE |
| | PERSON SIGNING AND SEALING EACH SHEET, ALSO SHEETS |
| | A-2.0 AND A-6.0 ARE MISSING THE PRINTED NAME OF THE |
| | PERSON RESPONSIBLE OF SIGNING AND SEALING SHEETS. PER |
| | FS 481 AND FAC61G16-23. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |