| 2007-12-21 14:19:05 | NOTE ADDED 12/21, |
| | |
| | DOES BUILDING CONTAIN A FIRE ALARM SYSTEM? |
| | IF SO, PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR |
| | MINIMUM LEVELS FOR STROBE AND HORN DEVICES FOR ADA |
| | COMPLIANCE. |
| 2007-12-21 12:27:43 | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE LISTED ON THE ELECTRICAL PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (WHERE APPLICABLE) |
| | |
| | 2) NOTE: PLEASE PROVIDE COMPLETE DETAILS AND |
| | INFORMATION FOR THE COMPLETE LIGHTING CONTROL SYSTEM. |
| | PLANS INDICATE THERE WILL BE A LUTRON XPS PANEL HOWEVER |
| | NO PANEL WAS SHOWN, NO DETAIL, NO SCHEDULING ETC. |
| | PLEASE SEE SOME AREAS/ROOMS WHICH ARE NOT SHOWING ANY |
| | LIGHTING CONTROLS. PLEASE SEE FOR EXAMPLE. ROOMS 137, |
| | 138, ACCENT LIGHTING ETC. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 3) NOTE: PLEASE SPECIFY THE METHOD OF LIGHTING BEING |
| | DESIGNED PER 13-415.2. PLANS APPEARS TO SHOW TABLE |
| | *C*? |
| | PLEASE VERIFY THE LIGHTING LEGEND AS THERE ARE FIXTURES |
| | ON TABLE WITH OUT DESIGNATIONS AFTER *F* FIXTURE AND |
| | NOT LOCATED ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE THE NEW SERVICE MAIN/METERAS |
| | SHOWN IS NOT PERMITTED PER 230.2. |
| | PLEASE SEE 230.2 AS THIS DOES NOT FALL UNDER EXCEPTION |
| | TO PERMIT A SEPARATE METER FOR THE SINGLE TENANT. |
| | PLEASE CONTACT THIS OFFICE TO GO OVER IF NEEDED OR |
| | REVISE PLANS ACCORDINGLY. |
| | |
| | 5) NOTE: PLEASE PROVIDE A SCHEDULE FOR THE EXISTING MDP |
| | SHOWING THE OVER CURRENT PROTECTION AND CONDUCTOR SIZES |
| | FOR PANELS. |
| | 240.4, 310.16 |
| | (NEED TO VERIFY FOR CODE COMPLIANCE AND LIFE SAFETY) |
| | FBC ADMIN 106.1.2 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-12-20 20:05:41 | 2007-12-20 20:05:41 |
| | IN ELEC FOR REVIEW |