| Plan Review Notes For Permit 07120146 |
| Permit Number |
07120146 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-02 18:06:27 | *****DENIED***** | | | | | | | | | 1.SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00, | | | THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED | | | NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT | | | THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A | | | COPY THEREOF. | | | | | | 2.SINCE THE SCOPE OF THE WORK IS GREATER THAN | | | $5,000.00, AS PER FLORIDA ADMINISTRATIVE CODES, A | | | PROFESSIONAL ENGINEER SHALL SIGN HIS SEAL TO ALL PLANS, | | | SPECIFICATIONS, ETC TO BE FILED FOR PUBLIC RECORD. THE | | | STAMPED ENGINEERED SEAL SHALL HAVE THE WORDING | | | "LICENSE" IN LIEU OF "CERTIFICATE". | | | | | | 3.PLEASE INDICATE IF THE NEWLY INSTALLED GENERATOR IS | | | FOR EMERGENCY USE OR FOR STANDBY POWER FOR FIRE | | | PROTECTION SYSTEMS OR BOTH. | | | | | | 4.IT IS INDICATED THAT THE PROPOSED EQUIPMENT WILL BE | | | A 500 GALLON DIESEL FUEL ENGINE GENERATOR.STORAGE AND | | | HANDLING OF FLAMMABLE LIQUIDS OR GASES SHALL BE IN | | | ACCORDANCE WITH NFPA 30 AND NFPA 54. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT.MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|