| 2007-12-12 12:33:25 | ** DENIED ** |
| | |
| | RED CROSS |
| | NEW GENERATOR INSTALL. |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS.(ELECTRICAL PLANS) |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | |
| | 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS SUBMITTED ARE |
| | REQUIRED TO CONTAIN AND PRINTED NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE PER FS 471.003, 489. |
| | |
| | 3) NOTE: PLEASE SPECIFY IF THE GENERATOR WILL BE A |
| | SEPARATELY DERIVED SYSTEM. |
| | PLEASE SEE NEC 250.30, 250.20 ETC AS A FOUR POLE ATS |
| | WOULD BE REQUIRED. |
| | |
| | 4) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR |
| | THE PROPOSED ATS. |
| | PLEASE ALSO SEE NOTES FROM FIRE AND MECHANICAL REVIEW |
| | FOR SPECS/CUT SHEETS FOR FUEL TANK ALSO. |
| | 90.7, 110.3 |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT AN OVER VIEW OF ALL ELECTRICAL |
| | EQUIPMENT AND LOCATIONS. |
| | PLEASE KNOW SOME ITEMS FOR REVIEW OF CODE COMPLIANCE |
| | CAN NOT BE DONE AT THIS TIME. |
| | 110.26,ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE 225.31-225.39 FOR REQUIRED |
| | DISCONNECTING MEANS FOR FEEDERS AT THE BUILDING. PLEASE |
| | SEE THERE IS AN EXCEPTION WHICH IS PROVIDED IN 700,701 |
| | AND 702 HOWEVER THE DISCONNECTING MEANS MUST BE *WITHIN |
| | SIGHT* AND *READILY ACCESSIBLE*. |
| | |
| | 7) NOTE: PLEASE PROVIDE INFORMATION ON PLANS WHETHER OR |
| | NOT THIS PROPOSED SYSTEM FEEDS ANY LEGALLY REQUIRED OR |
| | LIFE SAFETY SYSTEMS PER 700 OR 701. |
| | |
| | 8) NOTE: PLEASE PROVIDE A PANEL SCHEDULE SHOWING OVER |
| | CURRENT PROTECTION DEVICES, CONDUCTOR SIZES ETC FOR ALL |
| | BRANCH CIRCUITS TO GENERATOR CONTROL PANEL OR ANY OTHER |
| | SYSTEMS/DEVICES WHICH ARE BEING INSTALLED. |
| | FOR EXAMPLE: SHEET ATTACHED TO GENERATOR SPECS |
| | INDICATES HEATER ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NEC 310.16, 240.4, 408.4 |
| | |
| | 9) NOTE: PLEASE PROVIDE FURTHER INFORMATION AND |
| | CLARIFICATION OF THE *PROTOTYPE CERTIFICATION* SHEET |
| | SUBMITTED. |
| | PLEASE VERIFY UNIT IS LISTED AND CERTIFIED BY |
| | MANUFACTURE BEFORE AND AFTER INSTALL. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE KNOW A GENERAL CONTRACTOR WILL BE |
| | REQUIRED FOR THE BUILDING SCOPE OF WORK AS SHOWN ON |
| | PLANS. |
| | THIS COMMENT MAY BE PRESENT IN OTHER REVIEWS. |
| | |
| | 11) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS SUBMITTED |
| | ARE NOT SIGNED, OR SEALED BY THE ARCHITECT. |
| | FS 481.221 |
| | |
| | 12) NOTE: PLEASE LIST OCP AT THE GENERATOR. |
| | 310.16, 240.4, 445.13 |
| | SIZING OF CONDUCTORS CAN NOT BE VERIFIED AT THIS TIME |
| | PER 445.13 |
| | |
| | ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |