Plan Review Notes
Plan Review Notes For Permit 07120138
Permit Number 07120138
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-12-17 15:25:241. ON PAGE SE-801B THE 2006 EDITION OF NFPA 101, THE
 LIFE SAFETY CODE IS REFERENCED. NOTE SHOULD READ THE
 2003 EDITION OF THE LIFE SAFETY CODE WHICH COMPRISES
 PART OF THE FLORIDA FIRE PREVENTION CODE.
  
 2. APPROPRIATE EQUIPMENT TO ACCESS THE BUILDING SHALL
 BE PROVIDED IN THE KNOX-BOXES FOR THE RESCUE USE.
  
 3. WHAT PURPOSE DOES THE CARD READER LOCATED AT THE
 FIRE COMMAND ROOM PLAY. WHY IS ONE INSTALLED AT THIS
 LOCATION.
  
 4. IT WAS ALSO NOTED THAT CARD READERS ARE INSTALLED AT
 ELECTRICAL ROOMS AND MECHANICAL ROOMS. WHAT PURPOSE DO
 THESE SERVE.
  
 5. THE FIRE CODE REQUIRES THAT EXIT "DOORS SHALL BE
 ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE,
 WHENEVER THE BUILDING IS OCCUPIED". RE: NFPA 1, SECTION
 14.5.2.1
  
 6. THE ACCESS CONTROLLED EGRESS DOORS SHALL COMPLY WITH
 THE FIRE CODE REQUIREMENTS APPLICABLE TO THEIR USE.
  
 7. "DEVICES SHALL NOT BE INSTALLED IN CONNECTION WITH
 ANY DOOR ON WHICH PANIC HARDWARE OR FIRE EXIT HARDWARE
 IS REQUIRED WHERE SUCH DEVICES PREVENT OR ARE INTENDED
 TO PREVENT THE FREE USE OF THE DOORFOR PURPOSES OF
 EGRESS, UNLESS OTHER WISE PROVIDED IN 14.5.3"RE: NFPA
 1, SECTION 14.5.2.11
  
 8. ANY DEVICES USED ON STAIR DOORS SHALL COMPLY WITH
 "DOORS ON STAIR ENCLOSURES SHALL BE PERMITTED TO BE
 EQUIPPED WITH WITH HARDWARE THAT PREVENTS RE-ENTRY INTO
 THE INTERIOR OF THE BUILDING PROVIDED THAT THE
 FOLLOWING CRITERIA ARE MET:
  
 (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS
 POSSIBLE TO LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER
 EXIT
 (2) THERE SHALL NOT BE NOT MORE THAN FOUR INTERVENING
 BETWEEN STORIES WHERE IT IS POSSIBLE TO LEAVE THE STAIR
 ENCLOSURE TO ACCESS ANOTHER EXIT
 (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR NEXT
 TO TOP STORY THAT ALLOWS ACCESS TO ANOTHER EXIT (4)
 DOORS ALLOWING RE-ENTRY SHALL BE PROVIDED WITH A SIGN
 ON THE STAIR SIDE OF THE DOOR.
 (5) DOORS NOT ALLOWING RE-ENTRY SHALL BE PROVIDED WITH
 A SIGN ON THE STAIR SIDE INDICATING THE LOCATION OF THE
 NEAREST DOOR, IN EACH DIRECTION OF TRAVEL THAT ALLOWS
 RE-ENTRY OR EXIT.
  
 9. REQUEST TO EXIT MOTION SHALL BE INSTALLED ON ALL
 APPROPRIATE EXIT DOORS. DO NOT ASSUME THAT ONLY SOME
 DOORS WILL BE USED FOR EXITING AND SOME WILL NOT. ALL
 EXITS SHALL BE USEABLE.
  
 10. THE USE OF ELEVATORS BY FIRE RESCUE DURING
 NON-BUSINESS HOURS MUST BE CONSIDERED. THE GENERAL
 NOTES SECTION INDICATES THAT THE ELEVATORS WILL ONLY BE
 CONTROLLED BY CARD READERS DURING NON-BUSINESS HOURS.
  
 11. PLEASE EXPLAIN NOTE # 5 "AUTHORIZED PERSONNEL WILL
 BE ABLE TO DE-ACTIVATE THE ALARMS AND ENTER THE
 STAIRWELLS WITH A CARD SWIPE. DOES THIS NOTE MEAN THAT
 TRANSIENTS CANNOT ENTER THE STAIRWELLS WITHOUT A SWIPE
 CARD.
  
 12. HAS ANY MEMBER OF THE POLICE DEPARTMENT REVIEWED
 THE SECURITY PLAN AND MADE ANY RECOMMENDATIONS TO THESE
 PLANS.
  
 13. THE LEGEND INDICATED "KEY LOCK (PROVIDED BY
 OTHERS). PER NFPA 1, SECTION 14.5.2.2 "LOCKS IF
 PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, OR
 SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE".
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX