Plan Review Notes
Plan Review Notes For Permit 07120136
Permit Number 07120136
Review Stop B
Sequence Number 1
Notes
Date Text
2007-12-17 11:46:41****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE SHEET 10A, TWO DIFFERENT SETS OF DESIGN
 PRESSURES WERE GIVEN, TWO DIFFERENT ROOF HEIGHTS. ISN'T
 THIS ONE BUILDING?SHOULDN'T THERE BE ONLY ONE DESIGN
 PRESSURE FOR THE BUILDING, ASCE7-02, FBC1609? OR ARE
 THEY STRUCTURALLY TWO SEPARATE BUILDINGS?
  
 2.LEVEL 2 ALTERATION IS DECLARED, SHEET 2, PROJECT
 DESCRIPTION.SEE FBC EB CHAPTER 3, ARE NEW OPENINGS
 BEING CREATED?REPLACEMENT OF WINDOWS, EXISTING
 OPENINGS, IS A LEVEL 1 ALTERATION.
  
 3.INCLUDE 2007 AMENDMENTS IN GOVERNING CODE, SHEET
 10A AND OTHER PLACES.
  
 4.THE CAFF WINDOW, IF USED, WILL REQUIRE FLORIDA
 STATE PRODUCT APPROVAL.THIS MUST BE SUBMITTED PRIOR
 TO INSTALLATION AS ONLY THE KAWNEER 1600 HAS BEEN
 REVIEWED.