Plan Review Notes
Plan Review Notes For Permit 07120119
Permit Number 07120119
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-11 12:13:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 ROOM FINISH INDICATES PAINTED GWB. PAINTED
 GWB DOES NOT MEET THE REQUIREMENT FOR A HARD SURFACE
 REQUIRED IN SECTION 1210.2. (SMOOTH, HARD, NONABSORBENT
 SURFACE REQUIRED). PLEASE SHOW COMPLIANCE.
  
 2. SHT A-1 PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. PLEASE INDICATE THE LOCATION.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING UNLESS THE
 DRINKING FOUNTAIN IS A HI/LOW UNIT.
  
 4. SHT A-1 SHOW COMPLIANCE WITH THE FOLLING: ___FOR
 W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 ___FOR LAV:
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 *W/C SHALL BE 1'6" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE, AND THE LAV SHALL BE A MINIMUM OF 15" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIG.
 28.
  
 5. SHT P2.1 SUBMIT THE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE VACUUM SANITARY
 SYSTEM AS WELL AS FOR THE VACUUM VALVE ASSEMBLY.
 SECTIONS 301.7, 303.1, 303.2 & 303.4.
  
 6. SHT P2.1 THE FLOOR PLAN AND THE SANITARY RISER
 DIAGRAM SHALL SHOW THE CLEANOUT REQUIRED BY SECTION
 708.3.5, NEAR THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER. PLEASE SHOW ON THE FLOOR PLAN AND
 THE RISER DIAGRAM.
  
 7. SHT P2.1 AN RPZV BACKFLOW IS REQUIRE ON THE WATER
 SUPPLY TO THE BUILDING. SECTION 608.13.2. PLEASE SHOW
 OR INDICATE ON THE WATER RISER DIAGRAM.
  
 8. SHT P2.1 WATER RISER DIAGRAM. THE WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 9. ENERGY CALCULATION SHALL BE SIGNED, SEALED AND DATED
 BY THE DESIGN PROFESSIONAL. SECTION 13-103. THE OWNER'S
 AGENT SHALL ALSO SIGN THE CALCULATIONS.--NO
 INFORMATION IS GIVEN FOR THE INSTA HOT WATER HEATER.
 PLEASE SHOW REQUIREMENTS FOR THE WATER HEATER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]