Plan Review Notes
Plan Review Notes For Permit 07120119
Permit Number 07120119
Review Stop M
Sequence Number 1
Notes
Date Text
2007-12-06 15:02:06REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M0.1: THE SCHEDULE FOR VENTILATION DESIGN CONTAINS
 NO DATA. SHOW OUTSIDE AIR REQUIREMENTS IN ACCORDANCE
 WITH FBC, M 403.3 OR 403.4. ALSO, NOTE #3 CITES THE
 ASHRAE 50% RULE BASED ON ASHRAE 62 SEC 6.1.3.4. THIS
 APPEARS TO BE FROM ASHRAE 62-2001. AS THIS PLAN IS
 BEING SUBMITTED AFTER DECEMBER 8, 2006, THE CORRECT
 REFERENCE STANDARD IS ASHRAE 62.1-2004. SEC. 6.1.3.4 IS
 NOT A PART OF THIS STANDARD. OUTSIDE AIR VENTILATION
 SHALL BE DESIGNED IN ACCORDANCE WITH FBC, M TABLE 403.3
 OR ASHRAE 62.1-2004 IN ACCORDANCE WITH FBC, M 403.4.
 SEE FBC, M CHAPTER 15 FOR THE CORRECT REFERENCE
 STANDARDS.
  
 2. M0.1: HVAC GENERAL NOTE #11, MOVEABLE PARTS AND
 FIBERGLASS DUCTS SHALL ONLY BE PAINTED IF IT IS ALLOWED
 IN ACCORDANCE WITH THE LISTING OF THE ITEM BEING
 PAINTED. FBC, M 303.1
  
 3. M2.1: FOR AC-1, SHOW AUXILIARY DRAIN PROTECTION TO
 PREVENT CONDENSATE OVERFLOW IN ACCORDANCE WITH FBC, M
 307.2.3.
  
 4. M2.1: PROVIDE DETAIL SHOWING CONDENSING UNIT SECURED
 TO SLAB TO MEET MINIMUM WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBC, M 301.13 AND FBC 1609.
 NOTE: THE PRESCRIPTIVE METHOD OF ATTACHMENT LISTED IN
 FBC, M 301.13.1 APPLIES TO R-3 OCCUPANCIES ONLY.
  
 5. ENERGY: THE COMPLETION OF PROCEDURES DEMONSTRATING
 COMPLIANCE WITH THIS CODE FOR COMMERCIAL BUILDINGS
 SHALL BE SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER
 LICENSED TO PRACTICE IN THE STATE OF FLORIDA IN
 ACCORDANCE WITH FBC 13-103.1.1.1. ALSO, THE BUILDING?S
 OWNER, THE OWNER?S ARCHITECT, OR OTHER AUTHORIZED AGENT
 LEGALLY DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE
 BUILDING IS IN COMPLIANCE WITH THE CODE, AS PER SECTION
 553.907, FLORIDA STATUTES, PRIOR TO RECEIVING THE
 PERMIT TO BEGIN CONSTRUCTION OR RENOVATION IN
 ACCORDANCE WITH FBC 13-103.1.2. PROVIDE THESE MISSING
 ELEMENTS ON THE CERTIFICATIONS PAGE OF THE METHOD A
 FORMS.
  
 6: ENERGY: A COOLING LOAD CALCULATION SHALL BE
 PERFORMED FOR NEWLY INSTALLED UNITS. THIS CALCULATION
 (OR A SYSTEM SIZING SUMMARY, AS ALLOWED BY EXCEPTION 1)
 SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM SUBMITTED
 TO THE BUILDING DEPARTMENT WHEN THE BUILDING IS
 PERMITTED IN ACCORDANCE WITH FBC 13-407.1.ABC.1.
  
 7. ENERGY: HVAC SYSTEMS AND EQUIPMENT SHALL BE SIZED TO
 PROVIDE NO MORE THAN THE SPACE AND SYSTEM LOADS
 CALCULATED IN ACCORDANCE WITH SECTION 407.1.ABC.1 PER
 FBC 13-407.1.ABC.1.1.
  
 8. ENERGY: SHUTOFF DAMPER CONTROLS ARE REQUIRED. BOTH
 OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY
 SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.
 GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN
 SYSTEMS WITH A DESIGN OUTSIDE AIR INTAKE OR EXHAUST
 CAPACITY OF 300 CFM OR LESS.
  