| 2007-12-06 15:02:06 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. M0.1: THE SCHEDULE FOR VENTILATION DESIGN CONTAINS |
| | NO DATA. SHOW OUTSIDE AIR REQUIREMENTS IN ACCORDANCE |
| | WITH FBC, M 403.3 OR 403.4. ALSO, NOTE #3 CITES THE |
| | ASHRAE 50% RULE BASED ON ASHRAE 62 SEC 6.1.3.4. THIS |
| | APPEARS TO BE FROM ASHRAE 62-2001. AS THIS PLAN IS |
| | BEING SUBMITTED AFTER DECEMBER 8, 2006, THE CORRECT |
| | REFERENCE STANDARD IS ASHRAE 62.1-2004. SEC. 6.1.3.4 IS |
| | NOT A PART OF THIS STANDARD. OUTSIDE AIR VENTILATION |
| | SHALL BE DESIGNED IN ACCORDANCE WITH FBC, M TABLE 403.3 |
| | OR ASHRAE 62.1-2004 IN ACCORDANCE WITH FBC, M 403.4. |
| | SEE FBC, M CHAPTER 15 FOR THE CORRECT REFERENCE |
| | STANDARDS. |
| | |
| | 2. M0.1: HVAC GENERAL NOTE #11, MOVEABLE PARTS AND |
| | FIBERGLASS DUCTS SHALL ONLY BE PAINTED IF IT IS ALLOWED |
| | IN ACCORDANCE WITH THE LISTING OF THE ITEM BEING |
| | PAINTED. FBC, M 303.1 |
| | |
| | 3. M2.1: FOR AC-1, SHOW AUXILIARY DRAIN PROTECTION TO |
| | PREVENT CONDENSATE OVERFLOW IN ACCORDANCE WITH FBC, M |
| | 307.2.3. |
| | |
| | 4. M2.1: PROVIDE DETAIL SHOWING CONDENSING UNIT SECURED |
| | TO SLAB TO MEET MINIMUM WIND LOAD REQUIREMENTS IN |
| | ACCORDANCE WITH FBC, M 301.13 AND FBC 1609. |
| | NOTE: THE PRESCRIPTIVE METHOD OF ATTACHMENT LISTED IN |
| | FBC, M 301.13.1 APPLIES TO R-3 OCCUPANCIES ONLY. |
| | |
| | 5. ENERGY: THE COMPLETION OF PROCEDURES DEMONSTRATING |
| | COMPLIANCE WITH THIS CODE FOR COMMERCIAL BUILDINGS |
| | SHALL BE SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER |
| | LICENSED TO PRACTICE IN THE STATE OF FLORIDA IN |
| | ACCORDANCE WITH FBC 13-103.1.1.1. ALSO, THE BUILDING?S |
| | OWNER, THE OWNER?S ARCHITECT, OR OTHER AUTHORIZED AGENT |
| | LEGALLY DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE |
| | BUILDING IS IN COMPLIANCE WITH THE CODE, AS PER SECTION |
| | 553.907, FLORIDA STATUTES, PRIOR TO RECEIVING THE |
| | PERMIT TO BEGIN CONSTRUCTION OR RENOVATION IN |
| | ACCORDANCE WITH FBC 13-103.1.2. PROVIDE THESE MISSING |
| | ELEMENTS ON THE CERTIFICATIONS PAGE OF THE METHOD A |
| | FORMS. |
| | |
| | 6: ENERGY: A COOLING LOAD CALCULATION SHALL BE |
| | PERFORMED FOR NEWLY INSTALLED UNITS. THIS CALCULATION |
| | (OR A SYSTEM SIZING SUMMARY, AS ALLOWED BY EXCEPTION 1) |
| | SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM SUBMITTED |
| | TO THE BUILDING DEPARTMENT WHEN THE BUILDING IS |
| | PERMITTED IN ACCORDANCE WITH FBC 13-407.1.ABC.1. |
| | |
| | 7. ENERGY: HVAC SYSTEMS AND EQUIPMENT SHALL BE SIZED TO |
| | PROVIDE NO MORE THAN THE SPACE AND SYSTEM LOADS |
| | CALCULATED IN ACCORDANCE WITH SECTION 407.1.ABC.1 PER |
| | FBC 13-407.1.ABC.1.1. |
| | |
| | 8. ENERGY: SHUTOFF DAMPER CONTROLS ARE REQUIRED. BOTH |
| | OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL BE |
| | EQUIPPED WITH MOTORIZED DAMPERS THAT WILL AUTOMATICALLY |
| | SHUT WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE. |
| | GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN |
| | SYSTEMS WITH A DESIGN OUTSIDE AIR INTAKE OR EXHAUST |
| | CAPACITY OF 300 CFM OR LESS. |
| | |