Plan Review Notes
Plan Review Notes For Permit 07120119
Permit Number 07120119
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-12-28 15:55:50*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS REGISTERED IN OUR SYSTEM
 (8246) DOES NOT CORRELATE WITH THAT LISTED ON THE
 APPLICATION AND/OR IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET (8537).
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION,
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SCOPE OF OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE SAID PROPERTY AND/OF THE
 VICINITY THEREOF (INCLUDING STREETS ROADS, FIRELANES).
  
 4.ON SHEET A2, SHOW/DISPLAY THE NUMERICAL ADDRESS
 NUMBERS ON THE APPROPITE EXTERIOR ELEVATION.AS PER
 WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN
 6: IN HEIGHT AND NO LESS THAN 1" IN STROKE/WIDTH.
  
 5.DETAIL THE FLAME SPREAD CRITERIA FOR THE COVERED
 ENTRY AND NEW DECK.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW