Plan Review Notes
Plan Review Notes For Permit 07120119
Permit Number 07120119
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-07 14:47:55** DENIED REVIEW **
  
  
 1) NOTE: PLEASE SEE THE ADDRESS ON PLANS AND THAT ON
 APPLICATION STATES 8537, HOWEVER PCN LOCATION AS
 APPLIED IS 8264 NORTHLAKE BLVD.
 THIS IS BEING SENT TO THE ADDRESSING REVIEWER FOR
 COORDINATION.
 ONCE THE ADDRESS IS DETERMINED, PLEASE ADJUST ALL
 DOCUMENTS AND TITLE BLOCKS AS NEEDED.
 FBC 106.3.5.1.2, 106.1.2, FAC 61G1-16.004,
 61G15-23.002
  
 PLEASE SEE PLANS HAVE ONLY BEEN SUBMITTED FOR *PLAN
 REVIEW* AND NOT FOR PERMIT APPLICATION.
 PLEASE KNOW WHEN PLANS ARE COMPLETELY CODE COMPLIANT,
 PLANS WILL STILL REMAIN IN A FAILED STATUS UNTIL SUCH
 TIME APPLICATION FOR PERMIT IS MADE.
 LICENSING AND OTHER ITEMS ARE REVIEWED AT THAT TIME.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON PLANS. SOME MAY ALREADY BE PRESENT HOWEVER PLEASE
 INCLUDE THE FOLLOWING ON ELECTRICAL PLANS AS WELL.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
  
 3) NOTE: PLEASE SEE PLANS LIST THE OCCUPANCY AS
 *MERCANTILE*, PLEASE VERIFY THIS AS THERE ARE ITEMS
 UNDER THE NEC WHICH WOULD REQUIRE SOME ITEMS IF THIS IS
 INDEED A MERCANTILE OCCUPANCY. (600.5, 210.62?)
 PLEASE SEE THE ENERGY CALCULATIONS STATE *CONVENTION
 CENTER* WHICH IS NOT A MERCANTILE OCCUPANCY.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED WERE NOT SIGNED, DATED OR SEALED BY THE
 RESPONSIBLE DESIGNER(S).
 PLEASE SEE 13-103.1.1.1.
 PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON.
  
 5) NOTE: PLEASE BE SURE TO CORRELATE ALL INFORMATION
 PLACED IN THE INPUT DATA REPORT WITH THAT OF THE
 ELECTRICAL ON PLANS.
 FOR EXAMPLE:
 PLEASE SEE THE FIXTURE WATTAGES SHOWN ON THE FIXTURE
 LEGEND DO NOT CORRELATE WITH THE IDR.
 PLEASE SEE THE NUMBER OF FIXTURES ON PLANS DO NOT
 CORRELATE WITH THE IDR.
 ETC.
 PLEASE ALSO BE SURE THE CALCULATIONS CONTAIN THE SAME
 SQ FT AS STATED AND SHOWN ON PLANS.
 PLEASE SEE 13-415.1.A
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACED NOTES ON PLANS ACCORDINGLY.
  
 7) NOTE: PLEASE SEE RISER INDICATES AND *EQUIPMENT
 GROUNDING CONDUCTOR* FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT. PLEASE SEE 250.24 AND 250.6 AS EQUIPMENT
 GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 8) NOTE: PLEASE SEE THE GROUNDING ELECTRODE RISER AS
 THE FOOTER STEEL AS REQUIRED IS MISSING PER 250.50.
 AS THIS PROJECT CONTAINS BOTH BUILDING STEEL AND FOOTER
 STEEL BOTH ARE REQUIRED.
  
 9) NOTE: PLEASE SEE 13-415.1.ABC.1.1 AND PROVIDE
 VOLTAGE DROP FOR THE SERVICE ENTRANCE
 CONDUCTORS/FEEDERS.
  
 10) NOTE: PLEASE PROVIDE MANUFACTURES SPEC/CUT SHEETS
 FOR THE PROPOSED INST-HOT WATER HEATER.
 PLEASE BE SURE THE UNIT CONTAINS A LISTING FROM A NRTL.
 (NATIONALLY RECOGNIZED TESTING LABORATORY.
 90.7, 110.3.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.