Plan Review Notes
Plan Review Notes For Permit 07120119
Permit Number 07120119
Review Stop B
Sequence Number 1
Notes
Date Text
2007-12-13 15:40:17BUILDING PLAN REVIEW
 PERMIT: 07120119
 ADD: 8537 NORTHLAKE BLVD.
 CONT: "PLAN REVIEW" CONTACT: DANIEL ROBERGE
 TEL: (561) 644-7427
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS. SEE LS1 & S1 THE
 2006 IS REFRENENCED NOT THE 2007 FBC,PLEASE CORRECT.
  
 2)JOB LOCATION IS LOCATED IN A "A" FLOOD ZONE, AREA
 OF 100- YEAR FLOOD; BASE FLOOD ELEVATIONS & FLOOD
 HAZARD FACTORS NOT DETERMINED.FBC BUILDING 3110.1.2 /
 CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 3) NOTE, THE DESIGNER HAS CREATED THE BUILDING TYPE AS
 A BUILDING TYPE III-B, THE MINIMUM BUILDING
 CLASSIFICATION IS A TYPE V-B. SINCE THE DESIGNER HAS
 DESIGNED THIS BUILDING TO THE MORE CRITICAL III-B, THE
 BUILDING REVIEW WILL
 TAKE PLACE AS A TYPE III-B BUILDING.
 602.3 TYPE III.
 TYPE III CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN
 WHICH THE EXTERIOR WALLS ARE OF NONCOMBUSTIBLE
 MATERIALS AND THE INTERIOR BUILDING ELEMENTS ARE OF ANY
 MATERIAL PERMITTED BY THIS CODE. FIRE-RETARDANT-TREATED
 WOOD FRAMING COMPLYING WITH SECTION 2303.2 SHALL BE
 PERMITTED WITHIN EXTERIOR WALL ASSEMBLIES OF A 2-HOUR
 RATING OR LESS.
 THE BUILDING DOES HAVE A STEEL FRAMEWORK CREATING
 PORTIONS OF THE WALLS AS NON-BEARING BUT THERE ARE TWO
 OTHER ELEMENTS TO CONSIDER:
 3A) THE EXISTINGPAVILION IS LESS THAN 30'-0" AWAY
 FROM THE NEW STRUCTURE, TABLE 602 WOULD STILL REQUIRE 1
 HR FIRE RESISTANCE AS WELL AS NON-COMBUSTIBLE.
 3B) THE OTHER ISSUE IS THE LOFT (MEZZANINEL EVEL) WILL
 STILL MAKE THESE WALLS BEARING WALLS.
 PLEASE PROVIDE CODE COMPLIANCE.
  
 4) SHEET A1 INDICATES A LOFT, THIS TERM IS IN ACTUALITY
 A MEZZANINE, MEZZANINE . AN INTERMEDIATE LEVEL OR
 LEVELS BETWEEN THE FLOOR AND CEILING OF ANY STORY WITH
 AN AGGREGATE FLOOR AREA OF NOT MORE THAN ONE-THIRD OF
 THE AREA OF THE ROOM OR SPACE IN WHICH THE LEVEL OR
 LEVELS ARE LOCATED (SEE SECTION 505 ).MEZZANINES ARE
 WITHIN A ROOM AND SHALL NOT EXCEED 1/3 OF THAT ROOM OR
 SPACE IN WHICH THEY ARE LOCATED. PLEASE PROVIDE THE
 1/3RD AREA CALCULATION.
  
 5) IT APPEARS ONLY ONE SOILS REPORT FROM TIERRA WAS
 SUBMITTED, TWO SIGNED AND SEALED REPORTS WILL BE
 REQUIRED.1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) PLEASE HAVE THE SOILS ENGINEER REVIEW THE STRUCTURAL
 FOUNDATION SYSTEM. THE SOILS ENGINEER INDICATES THE USE
 OF A DEEP FOUNDATION SYSTEM, THE REPORT INDICATES USE
 OF A CONCRETE PILE SYSTEM WITH TEST PILING. NO WHERE IN
 THE SOILS REPORT DOES THE SOILS ENGINEEER INDICATE USE
 OF A SHALLOW FOUNDATION SYSTEM, REUSE OF EXISTING PILE
 OR THE USE OFHECICAL SCREW PILING. PLEASE SUBMIT
 INFORMATION ON THE HELICAL STEEL PILING. 1808.2.3
 SPECIAL TYPES OF PILES.
 THE USE OF TYPES OF PILES NOT SPECIFICALLY MENTIONED
 HEREIN IS PERMITTED, SUBJECT TO THE APPROVAL OF THE
 BUILDING OFFICIAL, UPON THE SUBMISSION OF ACCEPTABLE
 TEST DATA, CALCULATIONS AND OTHER INFORMATION RELATING
 TO THE STRUCTURAL PROPERTIES AND LOAD CAPACITY OF SUCH
 PILES. THE ALLOWABLE STRESSES SHALL NOT IN ANY CASE
 EXCEED THE LIMITATIONS SPECIFIED HEREIN. PLEASE HAVE
 THE SOILSREPORT REFLECT THE TYPE OF SYSTEMS TO BE
 INSTALED AT THIS PROJECT.
  
 7) NOTE ONLY ONE SET OF PRODUCT APPROVAL WERE SUBMITTED
 PLEASE PROVIDE TWO SETS 106.1.
  
 8) THE ROOFING REPORT SUBMITTED INDICATES THE
 SUBSYSTEMS TO ALL BE NON INSULATED SYSTEMS. SHEET A3
 AND A5 BOTH INDICATE A RIGID INSULATION SYSTEM, PLEASE
 PROVIDE THE CORRECT REPORT. 106.1.2.
  
 (9) SHEET A5 DETAIL# 5 INDICATES THE USE OF TRUSS
 ANCHORS, NO FLORIDA APPROVAL WAS SUBMITTED NOR PRODUCT
 TESTING REPORT. FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 TRUSS ANCHORS
 STAGGERED EDGE CEMENT FIBER SHINGLES- SIDING IF THIS IS
 A HARDI-PLANKCIRCLE THE SUBSYSTEM TO BE USED IN THE
 REPORT
 BOARD AND BATTEN- SIDING- IF THIS IS A HARDI-PLANK
 SUBSYSTEM CIRCLE THE SUBSYSTEM TO BE USED IN THE
 REPORT
  
 106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 10)SHEET A2 INDICATES THE USE OF CERTIFIED WOOD
 RAILING AND HANDRAIL SYSTEMS, PLEASE PROVIDE ADDITIONAL
 INFORMATION, 106.1.2.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  