2008-05-13 16:29:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** THIS REVIEW IS FOR PERMIT # 07120109, NOT FOR
 PREVIOUS APPLIED OR ISSUED PERMITS ***
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 12-12-07. SUBMIT ENERGY
 CALCULATIONS FOR REVIEW, SEE 2004 FBC 13-101.2.1.
  
 2) AS NOTED IN LAST REVIEW 12-12-07. SUBMITCOOLING
 LOAD CALCULATIONS (MANUAL J CALCULATIONS) FOR REVIEW,
 SEE 2004 FBC 13-607.1.ABC.1.
  
 3) PLEASE SUBMIT TWO NEW SETS OF MECHANICAL PLANS WITH
 OUT THE OLD CITY STAMPS AS THIS IS FOR A NEW PERMIT
 #07120112, PER 2004 FBC 106.1.1.
  
 4) PLEASE BE ADVISED THE REVISED MECHANICAL PLANS WILL
 NEED THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN, AND CONTRACTOR INFORMATION
 IF APPLICABLE ON THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]