Plan Review Notes
Plan Review Notes For Permit 07120085
Permit Number 07120085
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-04 14:39:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.REVISE APPLICATION; GOVERNING CODE IS FBC2004, NOT
 2005.
  
 2. ADDRESSED.
  
 3.AS DISCUSSED, ENGINEER HAS APPLIED FOR CERTIFICATE
 OF AUTHORIZATION.THIS ISSUE DOES NOT DELAY THE PERMIT
 PROCESS FOR THIS PERMIT.
  
 4-5. ADDRESSED.
  
 6.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 PLEASE PROVIDE THE FLORIDA STATE PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOORS.ONLY THE TEST REPORT WAS
 SUBMITTED.
  
 FOR THE WINDOWS, AN EXPIRED (2001) FLORIDA STATE
 PRODUCT APPROVAL WAS PROVIDED.PLEASE PROVIDE THE
 CURRENT APPROVAL, IF AVAILABLE.IF THIS IS NOT
 AVAILABLE, PLEASE CONFIRM WITH THE MANUFACTURER THAT
 THIS NOA IS IN COMPLIANCE WITH FBC2004 AS THE OLDER
 NOAS (ISSUED UNDER FBC2001) INCLUDED A 33% STRESS
 INCREASE WHICH IS NOT PERMITTED IN THE CURRENT CODE.
 SOME PRODUCTS REQUIRED AN DECREASE IN ANCHOR SPACING,
 OTHERS REVISED THE NOA TO USE ANCHORS WITH HIGHER
 VALUES.PLEASE CONFIRM THAT ANCHORING IS COMPLIANT
 WITHOUT THE STRESS INCREASE.
  
  
  
  