| 2007-12-10 09:38:05 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.REVISE APPLICATION; GOVERNING CODE IS FBC2004, NOT |
| | 2005. |
| | |
| | 2.A CERTIFICATE OF AUTHORIZATION IS REQUIRED FOR A & |
| | F ENGINEERING INC., FS481.219(2) (DAVID FORKEY PE). |
| | PROVIDE THE THE CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | THIS COMPANY OR SUBMIT AN APPLICATION TO FBPE AS |
| | REQUIRED AS THIS COMPANY HAS APPARENTLY BEEN IN |
| | BUSINESS SINCE 2001. |
| | |
| | 3.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES FOR |
| | BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING |
| | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| | ORIGINALS FAC61G15-23.002. |
| | |
| | 4.PROVIDE A COPY OF THE CONDO ASSOCIATION APPROVAL. |
| | |
| | 5.PROVIDE A FLOOR PLAN SHOWING WHERE THE SGDS AND |
| | WINDOWS WILL BE INSTALLED. |
| | |
| | 6.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG.INCLUDE THE |
| | EVALUATION REPORT AND INSTALLATION INSTRUCTIONS. |
| | NOTHING WAS PROVIDED FOR THE WINDOWS, EVALUATION |
| | REPORT/INSTALL INSTRUCTIONS WERE PROVIDED FOR THE SGD |
| | BUT NOT THE FL STATE PRODUCT APPROVAL. |
| | |
| | |
| | |