| 2008-03-26 12:39:39 | ** DENIEDREVIEW** |
| | |
| | ** PLANS HAVE NOW BEEN COMPLETELY REVISED WHICH HAS |
| | CREATE NEW COMMENTS. |
| | |
| | 1) NOTE: PLEASE PROVIDE INFORMATION ON THE EQUIPMENT |
| | WHICH IS NOW BEING PROPOSED WHICH IS LISTED AS A |
| | TRANSFER SWITCH AND BEING SERVICE ENTRANCE RATED. |
| | PLEASE SEE THE STATUTES REQUIRES A TRANSFER SWITCH |
| | WHICH IS ALSO DEFINED IN THE CODE. THIS MUST PROVIDE A |
| | FAIL-SAFE OPERATION FOR THOSE TWO SIDES OF INCOMING |
| | POWER FROM NORMAL AND EMERGENCY SO THAT IT IS NOT |
| | POSSIBLE FOR POWER TO BE FED INTO SERVICE AT ANY |
| | ONE-TIME. AS A*KEYED INTERLOCK*WHICH IS ONLY NOW |
| | BEING SHOWN, THIS DOES NOT PROVIDE THIS OPERATION. |
| | 702.6, 100, 110.3, 90.7 ETC. |
| | |
| | THIS IS A LIFE SAFETY, FIRE AND PROPERTY HAZARD. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |