Plan Review Notes
Plan Review Notes For Permit 07120059
Permit Number 07120059
Review Stop E
Sequence Number 3
Notes
Date Text
2008-03-26 12:39:39** DENIEDREVIEW**
  
 ** PLANS HAVE NOW BEEN COMPLETELY REVISED WHICH HAS
 CREATE NEW COMMENTS.
  
 1) NOTE: PLEASE PROVIDE INFORMATION ON THE EQUIPMENT
 WHICH IS NOW BEING PROPOSED WHICH IS LISTED AS A
 TRANSFER SWITCH AND BEING SERVICE ENTRANCE RATED.
 PLEASE SEE THE STATUTES REQUIRES A TRANSFER SWITCH
 WHICH IS ALSO DEFINED IN THE CODE. THIS MUST PROVIDE A
 FAIL-SAFE OPERATION FOR THOSE TWO SIDES OF INCOMING
 POWER FROM NORMAL AND EMERGENCY SO THAT IT IS NOT
 POSSIBLE FOR POWER TO BE FED INTO SERVICE AT ANY
 ONE-TIME. AS A*KEYED INTERLOCK*WHICH IS ONLY NOW
 BEING SHOWN, THIS DOES NOT PROVIDE THIS OPERATION.
 702.6, 100, 110.3, 90.7 ETC.
  
 THIS IS A LIFE SAFETY, FIRE AND PROPERTY HAZARD.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]