| 2008-04-10 09:56:38 | BUILDING PLAN REVIEW #3 4-9-08 |
| | PERMIT: 07120059 |
| | ADD: 2995 45TH STREET #562 |
| | CONT: R.D. LANGE CONST. INC. |
| | TEL: (863)661-6305 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 3RD |
| | ACTION: DENIED |
| | |
| | NOTE: THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2)OK |
| | |
| | **NOTED** SHEET COV-0 STATES PRODUCT APPROVAL NUMBERS |
| | FL4553/ FL1610.1 AND FL5115 HOWEVER, NONE OF THESE |
| | SHEETS WERE SUBMITTED. IF THESE ARE THE PRODUCT |
| | APPROVALS WHICH WILL BE USED ON THE PROJECT, PROVIDE |
| | THE STATE COVER SHEET ALONG WITH THE INSTALLATION |
| | REPORT INDICATING WHICH SYSTEM OR ITEMS WILL BE USED. |
| | SUBMIT THE STATE COVER SHEET WITH THE CORRECT |
| | INSTALLATION REPORTS. THE STATE COVER SHEET AND REPORT |
| | SHALL BE BOUND TOGETHER TO AVOID CONFUSION. |
| | |
| | 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL |
| | FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT |
| | APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT |
| | TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS |
| | ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED |
| | PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| | TEST. |
| | |
| | 4)OK. |
| | 5)OK. |
| | 6)OK |
| | 7)OK |
| | 8)OK |
| | 9)OK |
| | 10) OK |
| | 11) OK |
| | |
| | **NEW** |
| | GENERATOR INFORMATION REMOVED FROM PLANS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |