| Plan Review Notes For Permit 07120059 |
| Permit Number |
07120059 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-02-12 11:20:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION OF | | | THE PURPOSED DIESEL GENERATOR AND 1,200 GALLON FUEL | | | STORAGE TANK, SEE 2004 FBC/M 1301.2. | | | | | | *** INFORMATIONAL *** | | | A 1,200 GAL. FUEL TANK MUST BE 15 FT. FROM PROPERTY | | | LINE THAT IS OR CAN BE BUILT UPON. ALSO 5 FT. FROM | | | NEAREST SIDE OF ANY PUBLIC WAY. SEE 2003 N.F.P.A. 30 | | | CHAPTER 4 TABLE 4.3.2.1.1(B). | | | | | | ALSO THE PLAN WILL NEED TO GO TO PALM BEACH COUNTY | | | DEPT. OF ENVIRONMENTAL RESOURCES MANAGEMENT (PHONE | | | #561-233-2400) BEFORE RETURNING FOR A MECHANICAL | | | REVIEW. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|