2008-02-12 11:20:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION OF
 THE PURPOSED DIESEL GENERATOR AND 1,200 GALLON FUEL
 STORAGE TANK, SEE 2004 FBC/M 1301.2.
  
 *** INFORMATIONAL ***
 A 1,200 GAL. FUEL TANK MUST BE 15 FT. FROM PROPERTY
 LINE THAT IS OR CAN BE BUILT UPON. ALSO 5 FT. FROM
 NEAREST SIDE OF ANY PUBLIC WAY. SEE 2003 N.F.P.A. 30
 CHAPTER 4 TABLE 4.3.2.1.1(B).
  
 ALSO THE PLAN WILL NEED TO GO TO PALM BEACH COUNTY
 DEPT. OF ENVIRONMENTAL RESOURCES MANAGEMENT (PHONE
 #561-233-2400) BEFORE RETURNING FOR A MECHANICAL
 REVIEW.
  