2008-02-11 10:25:22** DENIED 2ND REVIEW **
  
 ** PLEASE SEE NEW NOTES BASED ON CHANGES MADE TO
 PLANS.
  
 1) NOTE: PLEASE SEE THE CODE REFERENCES ON PLANS STILL
 INDICATE THE 2002 NEC/ NFPA-70.
 PLEASE SEE THIS WAS DONE ON ELECTRICAL SHEETS HOWEVER
 PLEASE SEE SHEET COV -0.
 PLEASE ALSO BE SURE TO ADD NFPA-110 2002 FOR NEW
 GENERATOR.
 FBC 106.1.2 FOR COORDINATION.
  
 2) NOTE: PLEASE KNOW PLANS HAVE BEEN REVISED WITH NEW
 GENERATOR AS REQUIRED HOWEVER PLEASE SEE COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT PLANS.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR NEW
 PROPOSED GENERATOR, TRANSFER SWITCH AND SUB BASE FUEL
 TANK.
 THE FUEL TANK WILL BE UNDER REVIEW OF FIRE MARSHAL AND
 MECHANICAL REVIEW.
 PLEASE INDICATE THE ELEVATION LEVEL OF ANY OF THE
 REQUIRED EPSS SYSTEM EQUIPMENT INCLUDING GENERATOR PER
 CHAPTER 7 OF NFPA 7.2.3
 110.3, 90.7, NFPA-110
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE
 SCOPE OF WORK NOW ON PLANS NEEDS TO BE UPDATED PER FBC
 108.3
 PLEASE KNOW AS THE PLANS INCLUDE THE GENERATOR ETC THE
 COST INCLUDING LABOR, EQUIPMENT, MATERIALS, DESIGN COST
 ETC IS REQUIRED WHETHER OR NOT ANY OF THESE ITEMS ARE
 OWNER SUPPLIED.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES. AS MENTIONED
 IF ANY NEW LIGHTING WILL BE PROPOSED AS STATED ON
 ARCHITECTURAL PLANS. THESE MUST COMPLY WITH CHAPTER 13
 OF THE 2004 FBC W/2007 REVISIONS.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2 FOR
 REQUIRED LIGHTING PERFORMANCE CALCULATIONS.
  
 5) NOTE: PLEASE VERIFY GROUNDING AT THE GENERATOR. 250
 THERE IS NO INFORMATION ON TRANSFER SWITCH WHICH IS
 NEEDED.
 IS THIS SERVICE ENTRANCE RATED AS REQUIRED?
 IS THIS 3 OR 4-POLE? THIS WILL AFFECT THE GROUNDING AT
 THE GENERATOR.
 PLEASE SEE MANY QUESTIONS ARE OUTSTANDING WHICH MAY
 AFFECT REVIEW NOTES ON THE FOLLOWING REVIEW.
 230.70, 230.71, 250.20,250.50 ETC
 FBC 106.3.5.1.2 AND 106.1.2 FOR ADDITIONAL INFORMATION
 AND COORDINATION.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE/REVIEWER.
  