| Date |
Text |
| 2008-02-11 10:25:22 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE NEW NOTES BASED ON CHANGES MADE TO |
| | PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THE CODE REFERENCES ON PLANS STILL |
| | INDICATE THE 2002 NEC/ NFPA-70. |
| | PLEASE SEE THIS WAS DONE ON ELECTRICAL SHEETS HOWEVER |
| | PLEASE SEE SHEET COV -0. |
| | PLEASE ALSO BE SURE TO ADD NFPA-110 2002 FOR NEW |
| | GENERATOR. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 2) NOTE: PLEASE KNOW PLANS HAVE BEEN REVISED WITH NEW |
| | GENERATOR AS REQUIRED HOWEVER PLEASE SEE COMMENTS FROM |
| | OTHER TRADES WHICH WILL AFFECT PLANS. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR NEW |
| | PROPOSED GENERATOR, TRANSFER SWITCH AND SUB BASE FUEL |
| | TANK. |
| | THE FUEL TANK WILL BE UNDER REVIEW OF FIRE MARSHAL AND |
| | MECHANICAL REVIEW. |
| | PLEASE INDICATE THE ELEVATION LEVEL OF ANY OF THE |
| | REQUIRED EPSS SYSTEM EQUIPMENT INCLUDING GENERATOR PER |
| | CHAPTER 7 OF NFPA 7.2.3 |
| | 110.3, 90.7, NFPA-110 |
| | |
| | 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE |
| | SCOPE OF WORK NOW ON PLANS NEEDS TO BE UPDATED PER FBC |
| | 108.3 |
| | PLEASE KNOW AS THE PLANS INCLUDE THE GENERATOR ETC THE |
| | COST INCLUDING LABOR, EQUIPMENT, MATERIALS, DESIGN COST |
| | ETC IS REQUIRED WHETHER OR NOT ANY OF THESE ITEMS ARE |
| | OWNER SUPPLIED. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES. AS MENTIONED |
| | IF ANY NEW LIGHTING WILL BE PROPOSED AS STATED ON |
| | ARCHITECTURAL PLANS. THESE MUST COMPLY WITH CHAPTER 13 |
| | OF THE 2004 FBC W/2007 REVISIONS. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2 FOR |
| | REQUIRED LIGHTING PERFORMANCE CALCULATIONS. |
| | |
| | 5) NOTE: PLEASE VERIFY GROUNDING AT THE GENERATOR. 250 |
| | THERE IS NO INFORMATION ON TRANSFER SWITCH WHICH IS |
| | NEEDED. |
| | IS THIS SERVICE ENTRANCE RATED AS REQUIRED? |
| | IS THIS 3 OR 4-POLE? THIS WILL AFFECT THE GROUNDING AT |
| | THE GENERATOR. |
| | PLEASE SEE MANY QUESTIONS ARE OUTSTANDING WHICH MAY |
| | AFFECT REVIEW NOTES ON THE FOLLOWING REVIEW. |
| | 230.70, 230.71, 250.20,250.50 ETC |
| | FBC 106.3.5.1.2 AND 106.1.2 FOR ADDITIONAL INFORMATION |
| | AND COORDINATION. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE/REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |