| 2008-02-19 14:24:51 | BUILDING PLAN REVIEW |
| | PERMIT: 07120059 |
| | ADD: 2995 45TH STREET #562 |
| | CONT: R.D. LANGE CONST. INC. |
| | TEL: (863)661-6305 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND 2-19-08 |
| | ACTION: DENIED |
| | |
| | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2)NOTE: A ?DEMOLITION PERMIT? IS REQUIRED FOR THE |
| | INTERIOR DEMOLITION. EACH EXISTING BUILDING WHICH |
| | REQUIRES A PERMIT SHALL CONTAIN AN ASBESTOS |
| | NOTIFICATION STATEMENT WHICH INDICATES THE OWNER?S OR |
| | OPERATOR?S RESPONSIBILITY TO COMPLY WITH THE PROVISIONS |
| | OF SECTION 469.003, FLORIDA STATUTES, AND TO NOTIFY THE |
| | DEPARTMENT OF ENVIRONMENTAL PROTECTION OF HIS OR HER |
| | INTENTIONS TO REMOVE ASBESTOS, WHEN APPLICABLE, IN |
| | ACCORDANCE WITH STATE AND FEDERAL LAW. FBC: 105.9. |
| | |
| | **NOTED** HOWEVER, FL#2484-R1 IS MISSING THE |
| | INSTALLATION REPORT. FL#3393 CODE VERSION IS 2001. WE |
| | ARE PRESENTLY UNDER THE 2004 CODE VERSION. TWO APPROVED |
| | AND COMPLETE SEPARATE SETS OF PRODUCT APPROVALS SHALL |
| | BE SUBMITTED. IF THE GLAZING IS NON-IMPACT, PROVIDE THE |
| | PRODUCT APPROVAL FOR THE IMPACT PROTECTION (SHUTTERS). |
| | PLEASE MAKE SURE THAT THE INSTALLATION REPORT IS |
| | ATTATCHED TO EACH PRODUCT APPROVAL.** |
| | 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL |
| | FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT |
| | APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT |
| | TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS |
| | ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED |
| | PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| | TEST. |
| | |
| | 4)OK. |
| | 5)OK. |
| | 6)OK |
| | 7)OK |
| | 8)OK |
| | 9)OK |
| | 10) OK |
| | 11) OK |
| | |
| | **NEW** |
| | A) 61G1-16.004 TITLE BLOCK FOR MARK DAVID SHALL INCLUDE |
| | THE FOLLOWING INFORMATION. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | B)PROVIDE THE ENGINEERING CALCULATIONS FOR THE |
| | GENERATOR.THE CALCULATIONS SHALL INCLUDE THE ANCHORAGE |
| | AGAINST OVERTURNING, UPLIFT AND SLIDING PER 1609.1.3. |
| | INDICATE ON THE PLANS THE ELEVATION FOR THE GENERATOR |
| | SLAB.ALL INFORMATION REGUARDING THE SLAB NEEDS TO BE |
| | SHOWN ON THE PLANS ALONG WITH WIND DESIGN CRITERIA PER |
| | 1603.1.4. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | FAX (561) 805-6676 |
| | [email protected] |