Plan Review Notes
Plan Review Notes For Permit 07120059
Permit Number 07120059
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-18 08:51:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH AN ARCHITECTURAL TITLE BLOCK
 REQUIRES THE FIRM ADDRESS. THE ADDRESS ON THE TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS OF RECORD ON THE
 FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED SHEET).
 PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE BLOCK
 INFORMATION CORRELATE. FAC 61G1-16.004(1) & FS 481.219
 & 481.2055.
  
 2. PLUMBING SHEETS THE ENGINEER SHALL LEGIBLY INDICATE
 THEIR NAME ON EACH SHEET. FAC 61G15-23.002(2) & FS
 471.025.
  
 3. SHT P-1 KEY NOTES 20 & 21 NOT FOUND ON THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 4. SHT P-1 SHOWS A NEW 1-1/2" WATER SUPPLY CONNECTION
 OUTSIDE THE BUILDING, BUT THE WATER SUPPLY TO THE
 BUILDING IS SHOWN BY THE 3 COMPARTMENT SINK. PLEASE
 CLARIFY.SECTION 106.1.2.WILL THERE BE ANOTHER METER
 & BACKFLOW?
  
 5. SHT P-2 SANITARY RISER DIAGRAM ITEM P-4 IF THE SINK
 IS NOT INDIRECT WASTED, THEN IT SHALL BE VENTED.
 SECTION 901.2.1.
  
 6. SHT P-2 PLUMBING FIXTURE SCHEDULE INDICATES A P-10
 TRAP PRIMER. THIS IS NOT INDICATED ON THE FLOOR PLAN,
 SANITARY RISER DIAGRAM NOR ON THE WATER RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 7. SHT P-2 THE P-11 WATER FILTER SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT THE MANUF
 SPECIFICATIONS. SECTION 611.1.
  
 8. SHT P-3 WATER MANIFOLD/FILTER DETAIL SHOWS A 1-1/2"
 C.W. TO MEN'S REST ROOM. THIS IS NOT REFLECTED ON THE
 WATER RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved