| 2007-12-12 12:55:55 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07120059 |
| | ADD: 2995 45TH STREET #562 |
| | CONT: R.D. LANGE CONST. INC. |
| | TEL: (863)661-6305 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST 12/12/07 |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 REVISIONS. |
| | |
| | 2)NOTE: A ?DEMOLITION PERMIT? IS REQUIRED FOR THE |
| | INTERIOR DEMOLITION. EACH EXISTING BUILDING WHICH |
| | REQUIRES A PERMIT SHALL CONTAIN AN ASBESTOS |
| | NOTIFICATION STATEMENT WHICH INDICATES THE OWNER?S OR |
| | OPERATOR?S RESPONSIBILITY TO COMPLY WITH THE PROVISIONS |
| | OF SECTION 469.003, FLORIDA STATUTES, AND TO NOTIFY THE |
| | DEPARTMENT OF ENVIRONMENTAL PROTECTION OF HIS OR HER |
| | INTENTIONS TO REMOVE ASBESTOS, WHEN APPLICABLE, IN |
| | ACCORDANCE WITH STATE AND FEDERAL LAW. FBC: 105.9. |
| | |
| | |
| | 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS |
| | THAT ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL |
| | FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT |
| | APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT |
| | TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS |
| | ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED |
| | PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| | TEST. |
| | |
| | 4)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. SHEET A-1 REFERS TO |
| | SHEET F-3 FOR THE DOOR, FRAME AND FINISH SCHEDULE |
| | HOWEVER; SHEET F-3 IS MISSING FROM THE DRAWINGS. |
| | |
| | 5)SHEET A-1 REFERENCES A-3 AND A-4 FOR ADDITIONAL |
| | INFORMATION, THESE PAGES ARE NOT WITH THE SETS OF PLANS |
| | SUBMITTED. |
| | |
| | 6)FBC 105.9 EACH BUILDING WHICH REQUIRES A PERMIT FOR |
| | RENOVATION SHALL CONTAIN AN ASBESTOS NOTIFICATION |
| | STATEMENT WHICH INDICATES THE OWNER?S OPERATOR?S |
| | RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION |
| | 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT |
| | OF PROTECTION OF HIS OR HER INTENTIONS TO REMOVE |
| | ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH STATE AND |
| | FEDERAL LAW. |
| | |
| | 7)THE COUNTER AND CHECK-OUT AISLES SHALL MEET THE |
| | REQUIREMENTS OF FBC 11-7. SHOW THE ELEVATION DETAILS OF |
| | THE ACCESSIBLE COUNTER WHERE A POTION OF THE MAIN |
| | COUNTER SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND A |
| | MAXIMUM HEIGHT OF 36 INCHES. |
| | |
| | 8)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 9)1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND |
| | LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS |
| | GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM |
| | OF THE BUILDING: |
| | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | 3.WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | 5.COMPONENTS AND CLADDING. THE DESIGN WIND |
| | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE |
| | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS |
| | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 10)SUBMIT A WALL LEGEND WITH THE DIFFERENT TYPES OF |
| | WALL TO BE INSTALLED AT THIS PROJECT. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THE CODE. |
| | |
| | 11) A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOWING ALL |
| | MEANS OF EGRESS WHICH INCLUDE THE EXIT ACCESS, THE EXIT |
| | AND THE EXIT DISCHARGE. PER CH. 10 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |