| Plan Review Notes For Permit 07120054 |
| Permit Number |
07120054 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-10 08:32:52 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | 1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN | | | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE | | | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A | | | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT | | | OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16. | | | | | | 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR | | | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED. | | | | | | 3.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS | | | WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH | | | THE INSTALLATION SCHEDULE, ITEM 2 ABOVE. | | | | | | 4.SEE FBC1003.6, MEANS OF EGRESS CONTINUITY.THE | | | PATH OF EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT | | | BE INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A | | | MEANS OF EGRESS COMPONENT AS SPECIFIED IN CHAPTER 10. | | | HURRICANE SHUTTERS CANNOT BLOCK REQUIRED EXITS IN | | | COMMERCIAL BUILDINGS, EVEN IF OTHER EXITS ARE PROVIDED. |
|