| Plan Review Notes For Permit 07120041 |
| Permit Number |
07120041 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-11 13:45:05 | ***DENIED*** | | | | | | 1) PERMIT APPLICATION INDICATES INSTALLATION OF (1) | | | FLOW SWITCH AND (1) TAMPER SWITCH. THE DRAWINGS | | | ILLUSTRATE (2) TAMPER SWITCHES. PLEASE CORRELATE | | | INFORMATION. | | | | | | 2) PLEASE CLARIFY IF THE CONTROL PANEL IS EXISTING. | | | MANUFACTURER SPEC SHEETS SHOULD INCLUDE THE EQUIPMENT | | | THAT WILL BE INSTALLED. | | | | | | 3) PLEASE INDICATE THE TOTAL OCCUPANCY LOAD FOR THE | | | BUILDING. | | | | | | 4) NEW SYSTEMS THAT SUPERVISE AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM ARE REQUIRED TO BE UL CERTIFIED FOR | | | CENTRAL STATION SERVICE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|