Plan Review Notes
Plan Review Notes For Permit 07120023
Permit Number 07120023
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-28 11:33:03 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PLAN(UN NUMBERED) DESCRIBING THE PIPE SIZES,
 INDICATES "NO HEATER", THE SHEET (UN NUMBERED) THAT
 SHOWS ANCHOR POINTS INDICATES A HEATER, CORRELATE THE
 PLANS TO SHOW PROPOSED WORK.
  
 2} IF AN ELECTRIC HEATER IS BEING INSTALLED PROVIDE AN
 ELECTRICAL LOAD CALCULATION. CONSULT THE ELECTRICAL
 CONTRACTOR.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC. ALSO NUMBER THE SHEETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718