Plan Review Notes
Plan Review Notes For Permit 07120023
Permit Number 07120023
Review Stop P
Sequence Number 1
Notes
Date Text
2007-12-11 16:44:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. A PLUMBING PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 APPLIED FOR. INDICATE THE TYPE OF POOL EQUIPMENT BEING
 RELOCATED.THE SIZE OF THE EQUIPMENT PIPING. IF THERE IS
 A GAS POOL A GAS PERMIT WILL ALSO BE REQUIRED. PLEASE
 CLARIFY THIS ON THE RESUBMITTAL.
  
 2. FBC-2004 SEC. 424.2.7.2, OR
 FBCR-2004 SEC. R4101.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL REQUIRED)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy