| 2008-02-04 09:23:14 | NOTE ADDED: |
| | NEEDS ADDRESSING CLARIFICATION, PLANS SHOWS #205 YET |
| | THE APPLIED LOCATION ON PERMIT APPLICATION IS #200 AND |
| | 205 |
| 2008-02-04 09:20:38 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE KNOW THIS IS THE FIRST REVIEW WITH METHOD *C* |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE COORDINATE METHOD *C* WITH PLANS. FOR |
| | EXAMPLE: PLEASE SEE CONFERENCE ROOM 101 WHICH SHOWS TWO |
| | FIXTURES ON PLANS, YET THE INPUT DATA REPORT SHOWS ONLY |
| | ONE. |
| | PLEASE CONFIRM FIXTURE BALLAST VA RATING PER |
| | 13-415.2.ABC.1.2 (2). FIXTURES ARE SHOWN AS 3-32W |
| | BULBS, YET VA IS LESS.PLEASE CONFIRM EFFICACY OF |
| | BALLAST. |
| | 13-415.1.C, 13-415.2 |
| | PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED BEFORE |
| | RESUBMITTING. |
| | |
| | ** THE COMMENT IS MINOR AND ONLY NEEDS SOME ADJUSTMENTS |
| | BEFORE REVIEW CAN BE PASSED. UNLESS THE FIXTURE TYPE |
| | CHANGES, THE ELECTRICAL PLANS WERE STAMPED. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |