| 2008-04-01 07:17:36 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | COMMENT FROM PREVIOUS AUDIT: |
| | |
| | 4.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| | FS553.79 (2).HOW DOES THIS RENOVATION AFFECT THE FIRE |
| | SPRINKLER LAYOUT? |
| | |
| | 2ND AUDIT, NOT ADDRESSED.PROVIDE, AT A MINIMUM, A |
| | SPRINKLER HEAD LAYOUT AND SPECIFICATION.CALCULATIONS |
| | AND SHOP DRAWINGS MAY BE SUBMITTED AT THE TIME OF FIRE |
| | SPRINKLER PERMIT. |
| | |
| | 3RD AUDIT, ARCHITECT'S RESPONSE THAT THIS HAS BEEN |
| | REQUESTED IS NOTED, THANK YOU.PLEASE NOTE THAT THIS |
| | IS A STATUTORY REQUIREMENT AND CANNOT BE PROVISO'D. |
| | THEREFORE, THIS PERMIT WILL REMAIN IN FAILED STATUS |
| | UNTIL THE FIRE SPRINKLER PERMIT HAS BEEN REVIEWED AND |
| | IS READY TO BE ISSUED.PLEASE ADVISE WHEN THIS IS |
| | ISSUED AND THE STATUS WILL BE CHANGED TO "P". |
| | |
| | ***PLEASE NOTE THAT FIRE SPRINKLER PLANS REQUIRE |
| | PRIVATE PROVIDER REVIEW AS IT IS A PART OF THE BUILDING |
| | REVIEW*** |
| | |
| | NEW COMMENTS: |
| | |
| | 6.SHEET A7.1.2 HAS BEEN VOIDED PRIOR TO BUILDING |
| | REVIEW AS IT IS LACKING THE COMPLETE ADDRESS AND IS NOT |
| | INCLUDED IN THE INDEX SHEET.THIS SHEET IS REQUIRED AS |
| | IT INCLUDES BUILDING DETAILS. |
| | |
| | 7.PLEASE CLARIFY; LEVEL 6 IS REFERENCED ON SHEET |
| | A0.0.1 AND OTHER PLACES; SUITE NUMBER IS 700.ARE YOU |
| | USING A BRITISH STORY NUMBERING CONVENTION? |
| | |
| | |
| | |