| Date |
Text |
| 2007-12-06 12:36:48 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. PLANS TO BE ROUTED TO ADDRESSING TO DETERMINE SUITE |
| | NUMBER. ONCE ESTABLISHED THE SUITE NUMBER SHALL BE |
| | INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION |
| | 106.1.1. |
| | |
| | 2. SHT 2.6.1 BREAK ROOM SINK SHALL BE ACCESSIBLE. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.24.3 CLEARANCE |
| | B. 11-4.24.5 CLEAR FLOOR SPACE |
| | |
| | 3. SHT P7.6.1 ELECTRIC WATER HEATER DETAIL SHOWS A HUB |
| | DRAIN FOR THE INDIRECT WASTE OF THE EMERGENCY PAN DRAIN |
| | AND THE P & T VALVE OF THE WATER HEATER. ALSO SHOWN ON |
| | THE DETAIL IS A TRAP PRIMER. THESE ARE NOT SHOWN ON THE |
| | SANITARY RISER ISOMETRIC, NOR ON THE WATER RISER |
| | ISOMETRIC SHT P2.6.1.. PLEASE HAVE THE RISER DIAGRAMS |
| | REFLECT THE PIPING SHOWN ON THE WATER HEATER DETAIL. |
| | SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |