| 2008-04-01 06:46:09 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | COMMENT FROM FIRST AND SECOND AUDITS: |
| | |
| | 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| | FS553.79 (2). |
| | |
| | 2ND REVIEW; SPRINKLER PLANS NOT PROVIDED.HAS THIS |
| | BEEN APPLIED FOR SEPARATELY?A CLARIFICATION LETTER |
| | FROM DCA STATES "PLEASE NOTE THAT DESIGN DOCUMENTS, |
| | INCLUDING THE FIRE PROTECTION SPRINKLER SYSTEM (WHICH |
| | IS TO BE REVIEWED BY THE APPROPRIATE FIRE SAFETY |
| | INSPECTOR) ARE TO BE SUBMITTED TO YOU AT THE TIME OF |
| | PERMITTING, AND THAT THOSE DESIGNS MUST BE REVIEWED FOR |
| | COMPLIANCE AT THAT TIME BEFORE A PERMIT IS ISSUED." |
| | |
| | 3RD REVIEW, SPRINKLER PLANS NOT PROVIDED.ARCHITECT'S |
| | RESPONSE THAT THIS WILL BE UNDER SEPARATE PERMIT IS |
| | NOTED.AT A MINIMUM, A SPRINKLER HEAD LAYOUT PLAN IS |
| | TO BE SUBMITTED WITH THIS PERMIT FOR PERMIT ISSUANCE OR |
| | SUBMITTED SEPARATELY WITH COMPLETE INFORMATION FOR |
| | SPRINKLER PERMIT ISSUANCE. |
| | |
| | PLANS ARE OTHERWISE CODE COMPLIANT; WILL REMAIN IN |
| | FAILED STATUS UNTIL THE FIRE SPRINKLER PERMIT ISSUE IS |
| | RESOLVED, EITHER BY SUBMISSION AND REVIEW OF A CODE |
| | COMPLIANT SPRINKLER PERMIT (WHICH WOULD BE REQUIRED TO |
| | REMAIN IN F STATUS UNTIL THE TENANT BUILDOUT IS ISSUED) |
| | OR SUBMISSION AND REVIEW OF A SPRINKLER HEAD LAYOUT |
| | WITH THE TENANT BUILDOUT PERMIT. |
| | |
| | ***PLEASE ADVISE IF THIS ITEM IS ADDRESSED PRIOR TO |
| | RESUBMITTAL THROUGH SEPARATE PERMIT - STATUS WILL BE |
| | CHANGED TO "P"*** |
| | ***PLEASE NOTE THAT FIRE SPRINKLER PLANS REQUIRE |
| | PRIVATE PROVIDER REVIEW AS THIS IS A BUILDING |
| | REQUIREMENT*** |
| | |