| 2008-01-11 16:03:11 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.)ADDRESSED. |
| | |
| | 2.)PLEASE SEE MECHANICAL COMMENT #12.THE RESPONSE |
| | LETTER STATES THAT THE CONSTRUCTION MANAGER AND BASE |
| | BUILDING DEVELOPER WILL ISSUE THIS LETTER.I WAS |
| | UNABLE TO LOCATE THE LETTER IN THE PACKAGE. |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.FROM FIRST REVIEW - ON EITHER THE FLOOR PLAN OR THE |
| | LIFE SAFETY PLAN, PLEASE NOTE ALL REQUIRED FIRE |
| | RESISTANCE RATED ELEMENTS AND WALLS.SEE MECHANICAL |
| | SHEET H2.1.1, AN EXHAUST FAN IS SHOWN THROUGH THE WALL |
| | TO THE GARAGE AREA.ISN'T THERE AN OCCUPANCY |
| | SEPARATION AT THIS WALL?SEE FBC712, PENETRATIONS. |
| | |
| | 2ND REVIEW; 2 HOUR FIRE RATED WALLS SHOWN ON A2.1.5. |
| | PLEASE SEE SHEET A0.22, GROUND FLOOR PLAN (LIFE SAFETY) |
| | FOR THE BASE BUILDING, AND NOTE THE FOLLOWING: |
| | |
| | A.A 2 HOUR WALL IS SHOWN ON THE TENANT BUILDOUT PLAN |
| | BETWEEN THE BANK AND THE LOBBY.THIS IS NOT SHOWN ON |
| | THE BASE BUILDING.PLEASE NOTE THAT IT IS ACCEPTABLE |
| | TO EXCEED CODE COMPLIANCE, BUT IF NOTED ON THE PLAN AS |
| | HAVING A REQUIRED FIRE RESISTANCE RATING WILL BE |
| | TREATED AS SUCH. |
| | |
| | B.THE BASE BUILDING SHOWS A REQUIRED 2 HOUR OCCUPANCY |
| | SEPARATION BETWEEN THE PARKING GARAGE RAMP (NOTED ON |
| | THE PLAN AS "OPEN AIR RAMP AREA" AND "OUTSIDE WALL & |
| | CONC. RAMP") AND THE BANK.THE PLAN HAS BEEN REVISED |
| | TO SHOW OTHER FIRE RATED WALLS.PLEASE NOTE THE 2 HOUR |
| | REQUIREMENT AS REQUESTED OR CLARIFY HOW AND WHY THIS |
| | RATING REQUIREMENT HAS BEEN REMOVED.FIRE RESISTANCE |
| | RATINGS ARE REQUIRED ON PLANS TO EXPEDITE FIELD ISSUES |
| | WHICH MAY ARISE. |
| | |
| | 5.FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE |
| | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), |
| | FS553.79 (2). |
| | |
| | 2ND REVIEW; SPRINKLER PLANS NOT PROVIDED.HAS THIS |
| | BEEN APPLIED FOR SEPARATELY?A CLARIFICATION LETTER |
| | FROM DCA STATES "PLEASE NOTE THAT DESIGN DOCUMENTS, |
| | INCLUDING THE FIRE PROTECTION SPRINKLER SYSTEM (WHICH |
| | IS TO BE REVIEWED BY THE APPROPRIATE FIRE SAFETY |
| | INSPECTOR) ARE TO BE SUBMITTED TO YOU AT THE TIME OF |
| | PERMITTING, AND THAT THOSE DESIGNS MUST BE REVIEWED FOR |
| | COMPLIANCE AT THAT TIME BEFORE A PERMIT IS ISSUED." |
| | |
| | 6.SHOW MANEUVERING CLEARANCE, PULL SIDE, DOOR A119, |
| | FBC FIGURE 11-25. |
| | |
| | 7.BATHROOMS 114, 113, A2.1.4 SHOWS VWC AS WALL |
| | FINISH.THIS WAS NOT INCLUDED IN THE SCHEDULE OF |
| | FINISHES; PLEASE SEE FBC1210.2 REGARDING WALL FINISHES |
| | (BATHROOM, NONABSORBENT SURFACE REQUIRED).ALSO NOTE |
| | THAT THE DETAIL ROOM NUMBERS DO NOT CORRELATE (SHOWN AS |
| | 113/112), SHEET A3.1.1. |
| | |
| | 8.THE FLOOR PLAN AND BREAK ROOM 112 PLAN SHOWS A |
| | SINK, BUT THE DETAILS 111 (NOTE THAT THE ROOM |
| | DESIGNATION NUMBER DOES NOT CORRELATE WITH FLOOR PLAN) |
| | DO NOT SHOW A SINK, A3.1.1, AND CABINET DOORS ARE |
| | SHOWN.SEE FBC11-4.24.3, 11-4.24.5, KNEE CLEARANCE. |