| 2007-12-05 17:00:07 | NOTE ADDED, SPECS AND CUT SHEETS FOR UPS EQUIPMENT IS |
| | TO BE SUBMITTED FOR REVIEW. PLEASE BE SURE EQUIPMENT |
| | CONTAINS ALISTING FROM A NRTL. |
| | 90.7, 110.3 |
| 2007-12-05 12:57:33 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE SEE THE PERMIT APPLICATION AND |
| | SUPPORTING DOCUMENTS HAVE BEEN ROUTED TO THE ADDRESSING |
| | REVIEWER. |
| | THE PERMIT APPLICATION AS APPLIED INDICATES THE 1ST |
| | FLOOR HOWEVER THIS TENANT DOES NOT TAKE THE ENTIRE |
| | FLOOR AND WILL REQUIRE SUITE/UNIT #. |
| | PLEASE KNOW ONCE THIS HAS BEEN DETERMINED THE TITLE |
| | BLOCKS ARE TO BE REVISED INDICATING THIS ADJUSTMENT. |
| | FBC 106.1.2, 106.3.5.1.2, 106.5.3 ETC |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE BE SURE ALL ROOM AND AREA DESIGNATIONS |
| | ARE LISTED ON PLANS FOR SCOPE OF WORK BEING DONE UNDER |
| | THIS PERMIT APPLICATION. |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR ALL |
| | ELECTRICAL AS SHOWN AND CORRELATE WITH THE PANELS. |
| | FOR EXAMPLE: |
| | PANEL SCHEDULES INDICATE * OFFICE RECEPT* AND NOT THE |
| | ROOM OR AREA SPECIFIC. FOR EXAMPLE:PLEASE SEE |
| | 2-PUPS-10, PANEL SCHEDULE WORK ROOM AND PLANS WORK ROOM |
| | IS A CIRCUIT IN BREAK-ROOM 112. PLEASE SEE WORK ROOM |
| | WHICH IS 121 DOES NOT CALL FOR ROOM OR ARE ON PLANS. |
| | PLEASE ADJUST |
| | NEC 408.4, 310.16, 240.4 |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 3) NOTE: PLEASE GO OVER ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULES FOR |
| | LOADS. |
| | PLEASE CORRELATE ALL LOADS ON PANEL SCHEDULES WITH THAT |
| | OF THE LOADS SET FORTH IN THE NEC FOR RECEPTACLES AT |
| | 180VA PER YOKE. |
| | PLEASE CLARIFY HOW SOME ARE HIGHER OR LOWER PER |
| | CIRCUIT. WHAT VALUE IS BEING USED. |
| | PLEASE SEE NEC 220 .14/220.44. |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 4) NOTE: PLEASE KNOW THAT ELECTRICAL CONDUITS ARE FEEDS |
| | MAY NOT BE IN A SEPARATE BUILDING ON A SEPARATE |
| | PROPERTY WHICH IS FED FROM A COMPLETELY DIFFERENT |
| | ELECTRICAL SERVICE AND SYSTEM.225.30, 230.3, 90.4. |
| | PLANS NOTE THE DRIVE THRU AND TELLER AREAS WILL BE |
| | UNDER SEPARATE PERMIT WHICH IS OK, HOWEVER ELECTRICAL |
| | SYSTEMS MAY NOT BE MIXED AND CROSSED. |
| | ** PLEASE SEE FLORIDA STATUTES 655.962 FOR MINIMUM |
| | LIGHTING LEVELS REQUIRED FOR ATM/TELLER LOCATIONS. ** |
| | THIS IS ONLY NOTED FOR INFORMATION. |
| | |
| | 5) NOTE: PLEASE SEE PLANS FOR AREA/ROOM 105 AS THE |
| | LIGHTING FIXTURES ON PLANS ARE A HIGHER AMOUNT THAN ON |
| | THE LIGHTING PERFORMANCE CALCULATIONS. |
| | EXAMPLE: PLEASE SEE PLANS WITH 18 FIXTURES AND |
| | CALCULATIONS SHOW 17. APPEARS PLAN CONTAINS AN EXTRA |
| | MISPRINTED FIXTURE. |
| | |
| | 6) NOTE: PLEASE SEE COMMENTS FROM MECHANICAL REVIEW |
| | WITH RESPECT TO LOADS FOR AC AND FOR OTHER TRADES FOR |
| | ANY ITEMS WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |