| 2007-12-13 07:18:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. DRAWINGS SUBMITTED IN PENCIL ARE UNACCEPTABLE. ONE |
| | SET OF PLUMBING DRAWINGS ARE IN PENCIL. PER *106.1.3 |
| | QUALITY OF BUILDING PLANS. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION *106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) (9) PLUMBING, PLEASE |
| | SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM |
| | INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH |
| | CLEANOUT LOCATIONS. |
| | **THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM DOES |
| | NOT HAVE ALL WASTE AND TRAPS SIZED. |
| | |
| | 3. NOTE: SIZE THE INDICATED POTABLE WATER. PER |
| | *106.1.2, ADDITIONAL DATA. |
| | |
| | 4. THE INDICATED VENT TERMINATING THROUGH THE WALL |
| | SHALL COMPLY WITH THE FOLLWING AND BE INDICATED AS SUCH |
| | ON THE RESUBMITTAL. |
| | *904.6 EXTENSION THROUGH THE WALL. VENT TERMINALS |
| | EXTENDING THROUGH THE WALL SHALL TERMINATE A MINIMUM OF |
| | 10 FEET (3048 MM) FROM THE LOT LINE AND 10 FEET (3048 |
| | MM) ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL |
| | NOT TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH |
| | SOFFIT VENTS. SIDE WALL VENT TERMINALS SHALL BE |
| | PROTECTED TO PREVENT BIRDS OR RODENTS FROM ENTERING OR |
| | BLOCKING THE VENT OPENING. |
| | |
| | 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |