2007-12-13 07:18:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DRAWINGS SUBMITTED IN PENCIL ARE UNACCEPTABLE. ONE
 SET OF PLUMBING DRAWINGS ARE IN PENCIL. PER *106.1.3
 QUALITY OF BUILDING PLANS.
  
 2. PER FBC-2004 CHAPTER 1, SECTION *106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) (9) PLUMBING, PLEASE
 SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH
 CLEANOUT LOCATIONS.
 **THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT HAVE ALL WASTE AND TRAPS SIZED.
  
 3. NOTE: SIZE THE INDICATED POTABLE WATER. PER
 *106.1.2, ADDITIONAL DATA.
  
 4. THE INDICATED VENT TERMINATING THROUGH THE WALL
 SHALL COMPLY WITH THE FOLLWING AND BE INDICATED AS SUCH
 ON THE RESUBMITTAL.
 *904.6 EXTENSION THROUGH THE WALL. VENT TERMINALS
 EXTENDING THROUGH THE WALL SHALL TERMINATE A MINIMUM OF
 10 FEET (3048 MM) FROM THE LOT LINE AND 10 FEET (3048
 MM) ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL
 NOT TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH
 SOFFIT VENTS. SIDE WALL VENT TERMINALS SHALL BE
 PROTECTED TO PREVENT BIRDS OR RODENTS FROM ENTERING OR
 BLOCKING THE VENT OPENING.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]