| Plan Review Notes For Permit 07110748 |
| Permit Number |
07110748 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-04 15:09:34 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC 13-101.2. | | | | | | 2) SUBMITCOOLING LOAD CALCULATIONS (MANUAL J | | | CALCULATIONS), SEE 2004 FBC 13-607.1.ABC.1. | | | | | | 3) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLANS, SEE | | | 2004 FBC/R R303.3 EXCEPT. | | | | | | 4) SHOW THE CFM'S. AT ALL SUPPLY AIR GRILLS, SEE 2004 | | | WPB AMEND. 106.3.5.4 (10). | | | | | | 5) SHOW THE SEER OF THE A/C SYSTEM ON THE MECHANICAL | | | PLAN. | | | | | | 6) SHOW THE TOTAL COOLING BTU'S FOR THE A/C SYSTEM ON | | | THE MECHANICAL PLANS. | | | | | | 7) SHOW THE HEATER KW OR STATE NO HEAT ON THE | | | MECHANICAL PLAN. | | | | | | 8) THE MECHANICAL PLANS NEED THE SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN (ALLAN WERITZ), AND | | | CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE | | | W.P.B. AMEND. 106.1.3. | | | | | | 1 MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|