Plan Review Notes
Plan Review Notes For Permit 07110748
Permit Number 07110748
Review Stop M
Sequence Number 1
Notes
Date Text
2007-12-04 15:09:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC 13-101.2.
  
 2) SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS), SEE 2004 FBC 13-607.1.ABC.1.
  
 3) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLANS, SEE
 2004 FBC/R R303.3 EXCEPT.
  
 4) SHOW THE CFM'S. AT ALL SUPPLY AIR GRILLS, SEE 2004
 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW THE SEER OF THE A/C SYSTEM ON THE MECHANICAL
 PLAN.
  
 6) SHOW THE TOTAL COOLING BTU'S FOR THE A/C SYSTEM ON
 THE MECHANICAL PLANS.
  
 7) SHOW THE HEATER KW OR STATE NO HEAT ON THE
 MECHANICAL PLAN.
  
 8) THE MECHANICAL PLANS NEED THE SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN (ALLAN WERITZ), AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 1 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]