| Plan Review Notes For Permit 07110748 |
| Permit Number |
07110748 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-04 11:55:35 | | | | | | | | | | APPLICATION #07110748 | | | ELECTRICAL PLAN REVIEW | | | 516 51ST STREET | | | 12/3/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | 1} SHOW COMPLIANCE WITH THE RECEPTACLE SPACING | | | REQUIREMENTS OF 210.52. | | | | | | 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | | (3). | | | | | | 3} COMPLY WITH 210.70 LIGHTING REQUIREMENTS, INTERIOR | | | AND EXTERIOR. | | | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|