| Plan Review Notes For Permit 07110731 |
| Permit Number |
07110731 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-11-08 14:14:21 | PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND | | | STAMPED. REVIEW IS NOT PASSED DUE TO FAILED REVIEW OF | | | ENERGY CALCULATIONS. | | | | | | ENERGY CALCS: THE EFFICIENCIES LISTED IN THE INPUT | | | REPORT (IR) DO NOT CORRESPOND WITH THE FAN RATINGS | | | SHOWN ON THE MECHANICAL AND ELECTRICAL PLANS. | | | EXAMPLE: AHU-1 IN THE IR SHOWS AN EFFICIENCY OF 1.25. | | | THE EFFICIENCY IS DETERMINED USING THE FORMULA | | | CFM/WATTS. AHU-1 CALLS FOR 10,800 CFM AND ELECTRICAL | | | PLANS SHOW THE FAN FOR AHU-1 RATED AT 16.7 KVA OR | | | 16,700 WATTS. THIS GIVES AN EFFICIENCY RATING FOR AHU-1 | | | OF 0.65, WELL BELOW THE 1.25 RATING SHOWN ON THE IR. | | | PLEASE CHECK THIS AND ALL OTHER AHU FANS AND MAKE THE | | | NECESSARY CORRECTIONS IN THE INPUT REPORT. | | | | | | IF SOMEONE WOULD LIKE TO CONTACT ME TO DISCUSS THE | | | POSSIBILITY OF CORRECTING THE ENERGY CALCULATIONS | | | DURING THIS REVIEW CYCLE, PLEASE CONTACT ME AT THE | | | PHONE NUMBER OR EMAIL ADDRESS LISTED BELOW. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|