Plan Review Notes
Plan Review Notes For Permit 07110731
Permit Number 07110731
Review Stop M
Sequence Number 3
Notes
Date Text
2008-11-08 14:14:21PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. REVIEW IS NOT PASSED DUE TO FAILED REVIEW OF
 ENERGY CALCULATIONS.
  
 ENERGY CALCS: THE EFFICIENCIES LISTED IN THE INPUT
 REPORT (IR) DO NOT CORRESPOND WITH THE FAN RATINGS
 SHOWN ON THE MECHANICAL AND ELECTRICAL PLANS.
 EXAMPLE: AHU-1 IN THE IR SHOWS AN EFFICIENCY OF 1.25.
 THE EFFICIENCY IS DETERMINED USING THE FORMULA
 CFM/WATTS. AHU-1 CALLS FOR 10,800 CFM AND ELECTRICAL
 PLANS SHOW THE FAN FOR AHU-1 RATED AT 16.7 KVA OR
 16,700 WATTS. THIS GIVES AN EFFICIENCY RATING FOR AHU-1
 OF 0.65, WELL BELOW THE 1.25 RATING SHOWN ON THE IR.
 PLEASE CHECK THIS AND ALL OTHER AHU FANS AND MAKE THE
 NECESSARY CORRECTIONS IN THE INPUT REPORT.
  
 IF SOMEONE WOULD LIKE TO CONTACT ME TO DISCUSS THE
 POSSIBILITY OF CORRECTING THE ENERGY CALCULATIONS
 DURING THIS REVIEW CYCLE, PLEASE CONTACT ME AT THE
 PHONE NUMBER OR EMAIL ADDRESS LISTED BELOW.
  