| Plan Review Notes For Permit 07110731 |
| Permit Number |
07110731 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-11-13 16:12:56 | 900 BRANDYWINE RD | | | UNITED METHODIST CHURCH | | | NOV.13,2008 | | | | | | | | | | | | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 07110731 | | | ADD: 900 BRANDYWINE RD | | | CONT: HEDRICK BROTHERS | | | TEL: (561)281-7530 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: | | | | | | ENERGY CALCULATIONS: | | | | | | 1) IN THE INPUT DATA REPORT, FLOORS, HAVE TAKEN A VALUE | | | OF 5.73 FOR THE TOTAL AREA OF THE BUILDING. FOR | | | CONCRETE FLOOR, IN ELECTRIC ROOMS, MECHANICAL, JANITORS | | | COLOSETS. THE SAME VALUE FOR CARPET AND PADDING ALSO | | | WAS TAKEN FOR CERAMIC TILE FLOORS, THE ENERGY CODE | | | APPENDIX-B 2.5.2 FOR MASS FLOORS. PLEASE REVIEW U- | | | FACTORS IF THE INSULATION IS NOT CONTINUOUS. | | | | | | THIS ITEM PLUS THE MECHANICAL REVIEW COMMENT RELATED TO | | | THE ENRGY CODE WILL HAVE AN EFFECT ON THE OUTCOME OF | | | THE BUILDING END USE SCORE OF 99.44. | | | | | | BOTH THE MECHANICAL AND BUILDING REVIEWERS WILL ACCEPT | | | NEW ENERGY CALCULATION FOR THIS REVIEW. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|