| Plan Review Notes For Permit 07110731 |
| Permit Number |
07110731 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-03 23:20:56 | *****DENIED***** | | | | | | | | | 05. ON SHEET FP 4 IN THE DOUBLE CHECK DETECTOR ASSEMBLY | | | DETAIL, INDICATE IN THE NOTES AND/OR ILLUSTRATE THAT | | | THE DEVICE IS TO BE CHAINED AND LOCKED (AS PER WEST | | | PALM BEACH FIRE PREVENTION BUREAU) . | | | | | | 08. ON SHEET A-0.1.1, PROVIDE THE OCCUPANT LOAD LOAD | | | FOR THIS NEW ASSEMBLY STRUCTURE, AS IN THE NUMBER OF | | | PERSONS WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE | | | REQUIRED. | | | | | | 17. PLEASE NOTE AND (OR) ILLUSTRATE ON AN APPROPIATE | | | PLAN SHEET THAT KNOX LOCKING CAPS WILL BE REQUIRED ON | | | FIRE DEPARTMENT CONNECTION (FDC). FOR APPLICATIONS, | | | CONTACT WEST PALM BEACH FIRE PREVENTION BUREAU AT | | | 561-804-4724. | | | | | | | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|