| 2007-12-26 16:52:48 | 900 BRANDYWINE RD |
| | UNITED METHODIST CHURCH |
| | DEC.28, 2007 |
| | |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07110731 |
| | ADD: 900 BRANDYWINE RD |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)281-7530 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| | RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| | BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| | SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM |
| | BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 REVISIONS PLEASE REVISE YOUR |
| | CODE SUMMARY FOUND ON SHEET A-0.1.1. |
| | |
| | 2( SHEET A-0.1.1: |
| | 2A) THE PLANS APPEAR TO HAVE CODE TERMINOLOGY THAT IS |
| | FOUND UNDER THE 2001 FBC THE BUILDING, (NEW) IS LABEL |
| | BUILDING TYPE II SPRINKLED AND A-1 ASSEMBLY LARGE. |
| | PLEASE SEE TABLE 503 FOR THE ALLOWABLE HEIGHT AND AREAS |
| | FOR A A-3 OCCUPANCY (CHURCH) FOR AND DECLARE THE |
| | MINIMUM BUILDING TYPE. 602.1.1 FOUND IN THE 2004 FBC. |
| | IF AREA INCREASES ARE TO BE TAKEN PLEASE INDICATE THE |
| | CALCULATIONS WHERE THESE INCREASES WERE TAKEN. PLEASE |
| | SEE UNLIMITED AREA UNDER 507.5 IS FOR A SINGLE STORY |
| | BUILDING, SHEET A-2.2.1 INDICATES A SECOND STORY |
| | LOCATED WITHIN THE BUILDING. |
| | |
| | 2B) CODE SUMMARY STRUCTURAL ELEMENTS, THE HOUR RATINGS |
| | AND FOOTNOTES FOUND IN THIS SECTION ARE ALSO TAKEN FROM |
| | THE 2001 FBC, PLEASE REVIEW AND UPDATE TO THE 2004 FBC |
| | SEE TABLE 601, TABLE 602 & TABLE 704.8. |
| | |
| | 2C) BUILDING INFORMATION MAKES IT UNCLEAR AS TO WHAT |
| | BUILDING TYPE IS BEING INDICATED, THERE IS A EXISTING |
| | BUILDING AND A NEW BUILDING SQUARE FOOTAGE PROVIDED, |
| | THEN A TOTAL BUILDING FOOTPRINT. IF THIS TO BE TWO |
| | SEPARATE BUILDINGS WITH A PROPOSED FIREWALL LEAVE OFF |
| | THE TOTAL BUILDING FIGURE, THEY WOULD BE CONSIDERED TWO |
| | SEPARATE BUILDINGS. IF DESIGNING TO THE MORE CRITICAL |
| | TYPE I-B FOR THE TOTAL BUILDING THE AREA IS UNLIMITED. |
| | 106.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET A-2.1.3: DISCREPANCY, PLEASE SEE DOOR NUMBER |
| | A126 & C126 THE TWO DOORS HAVE A COMBINED OCCUPANT LOAD |
| | OF 194 ALSO LOOK AT THE EGRESS PATH TO DOOR 126B AND |
| | THE OCCUPANT LOAD REFLECTED ON THE PLAN IS ONLY159 THIS |
| | IS LOWER THAN THE 194 REGRESSING THROUGH THE 2 PAIR OF |
| | DOUBLE DOORS PLUS AN ADDITIONAL 5 FROM THE EXIT ACCESS |
| | CORRIDOR HEADING TOWARDS THIS EXIT DOORWAY. THIS IS |
| | CREATING A CONVERGING EXIT AT A DOORWAY THAT CAN ONLY |
| | HANDLE 170 THROUGH THE DOOR. 1004.5 CONVERGING EXITS. |
| | |
| | 4A) SHEET A-2.1.3 & A2.1.1, THE CONTINUATION OF THE |
| | EGRESS PATH FROM DOOR 126B LEADS TO A EXTERIOR SIDEWALK |
| | INTO WHAT APPEARS TO BE A EGRESS COURT AND THROUGH THE |
| | COVERED WALKWAY OF THE EXISTING BUILDING. 705.1 FIRE |
| | WALLS SERVING TO CREATE SEPARATE BUILDINGS, THEREFORE |
| | ALL PROVISIONS OF THE CODE INCLUDING HEIGHT AND AREA |
| | LIMITATIONS, FIRE PROTECTION SYSTEMS AND MEANS OF |
| | EGRESS ARE TO BE APPLIED INDIVIDUALLY TO EACH BUILDING. |
| | IF THE COVERED WALKWAY FROM THE EXISTING BUILDING IS TO |
| | BE CONSIDERED PART OF THE EGRESS PATH FROM THE COURT |
| | AREA SOME ADDITIONAL INFORMATION WILL BE REQUIRED. 4B) |
| | THE PLANS INDICATE THE EXISTING BUILDING TO BE A TYPE V |
| | BUILDING, IS THIS A 2001 OR 2004 TYPE V? 4C) PLANS |
| | INDICATE THIS EXTERIOR WALL NOT HAVING ANY WINDOWS |
| | WITHIN THE COVERED WALKWAY WHICH WOULD CREATE A FIRE |
| | HAZARD REQUIRING FIRE RATED OPENING PROTECTIVE? 4D) THE |
| | OTHER ISSUE IS THE PLAN ALSO INDICATE THE EXISTING WALL |
| | TO HAVE A WALL IDENTIFICATION TAG AS A 710, A 2HR RATED |
| | WALL WITH CORE FILL 500, IS THIS WALL ALREADY |
| | CONSTRUCTED THIS WAY? |
| | |
| | 1023.5.2 CONSTRUCTION AND OPENINGS OF EGRESS COURTS |
| | WHERE AN EGRESS COURT SERVING A BUILDING OR PORTION |
| | THEREOF IS LESS THAN 10 FEET (3048 MM) IN WIDTH, THE |
| | EGRESS COURT WALLS SHALL BE NOT LESS THAN 1-HOUR |
| | FIRE-RESISTANCE-RATED EXTERIOR WALLS COMPLYING WITH |
| | SECTION 704 FOR A DISTANCE OF 10 FEET (3048 MM) ABOVE |
| | THE FLOOR OF THE COURT , AND OPENINGS THEREIN SHALL BE |
| | EQUIPPED WITH FIXED OR SELF-CLOSING, ?-HOUR OPENING |
| | PROTECTIVE ASSEMBLIES. |
| | |
| | 4E) NOTE THE NEW FLAT DECKS CREATED ON THE EXISTING |
| | BUILDING WILL CREATE ADDITIONAL ROOF CONTRIBUTIONS SEE |
| | A-5.1.2 & A5.1.6 SEE PLUMBING COMMENTS FOR ADDITIONAL |
| | INFORMATION FOR ROOF DRAINAGE. |
| | |
| | 4F) THE EXISTING TWO STORY CHAPEL, IS THERE OPENINGS |
| | ABOVE THE SLOPED ROOF SECTIONS , THE NEW HORIZONTAL |
| | ROOF DECKS? 705.6.1. |
| | |
| | 5) SHEET A-2.1.3 DISCREPANCY, PLEASE SEE CHOIR |
| | REHEARSAL ROOM 153 AND SHEET A-2.1.1 ON THIS SHEET |
| | CORRIDORS 152 & 157 ARE BLOCKED BY A WALL NOT SHOWN ON |
| | SHEET A-2.1.3. 106.1.2 ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 6) PLEASE PROVIDE CODE COMPLIANCE WITH TABLE 1016.1FOR |
| | ASSEMBLY OCCUPANCIES GREATER THAN 30 THE CORRIDORS ARE |
| | TO BE FIRE RATED 1 HR EVEN WITH FIRE SPRINKLERS. |
| | CORRIDORS, 111, 118 & 120 DO NOT INDICATE RATED WALLS |
| | AND OPENING PROTECTIVE ON DOOR AND WINDOW OPENINGS |
| | TABLE 715.3. PLEASE PROVIDE CODE COMPLIANCE WITH THIS |
| | SITUATION. |
| | |
| | 7) PLEASE SEE M-2.1.0 WHERE MECHANICAL DUCTS CROSS |
| | RATED WALLS WITHOUT THE INSTALLATION OF RATED DAMPERS, |
| | 712.3.3 DUCTS AND AIR TRANSFER OPENINGS. |
| | |
| | 8) PLEASE PROVIDE ON LIFE SAFETY SHEET A-2.1.3 WHICH |
| | DESIGN METHOD WAS USED 1024.6.1 WITHOUT SMOKE |
| | PROTECTION OR 1024.6.2 SMOKE PROTECTED SEATING. |
| | |
| | 9) PLEASE SEE A-2.1.1 & A2.1.3 BOTH PLANS INDICATE THE |
| | USE OF RAMPS 3/4" /12". SEE DEFINITION OF RAMP 11-3 A |
| | WALKING SURFACE WHICH HAS A RUNNING SLOPE GREATER THAN |
| | 1:20. SEE 11-4.8.5 WHERE HANDRAILS WILL BE REQUIRED, |
| | HORIZONTAL PROJECTIONS GRATER THAN 72". |
| | |
| | 10) A-2.1.1 & A2.1.3 BOTH PLANS INDICATE THE USE OF AN |
| | ELECTRIC LIFT, PLEASE PROVIDE CODE COMPLIANCE |
| | INFORMATION ON LIFT11-4.1.3, EXCEPTION# 4. |
| | |
| | 11) A-2.1.1 & A-2.1.3 BOTH STAIRS BY DOORS A126 & A143 |
| | BOTH HAVE F.E.C. THIS ABBREVIATION IS NOT LISTED ON |
| | A-0.1.1 ARCHITECTURAL ABBREVIATIONS, 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 12) SHEET A-2.1.1& A-2.1.3 BOTH INDICATE CLASSROOM 1 |
| | ROOM# 1 AND DOOR# B172, THIS DOOR IS MISSING THE CLEAR |
| | FLOOR SPACE (18") LATCH SIDE OF THE DOOR. 11-4.13.5 |
| | DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM |
| | CLEAR WIDTH OF 32" WITH THE DOOR OPEN 90-DEGREES, |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND OPPOSITE |
| | STOP. |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 13) SHEET A-2.1.1 & A2.1.3 DISCREPANCY SHEET A-2.1.1 IS |
| | MISSING OPENINGS INTO THE RESTROOMS 150 & 159 FROM THE |
| | VESTIBULES, 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 14) SHEET A-2.11 & A-2.1.3 THERE APPEARS TO BE A |
| | DISCREPANCY IN THE RAMP AT THE ENTRY POINT 146, |
| | A-12.1.1 INDICATES A DIFFERENCE OF 5" BUT THE RAMP IS |
| | NOT CLEARLY MARKED WHEREAS ON A-2.1.3 THE RAMP SHOWS |
| | EXPANSION JOINTS SPREAD AT 14'-0" APART? 11.4.8.5. |
| | HANDRAILS: IF A RAMP HAS A RISE GREATER THAN 6" OR A |
| | HORIZONTAL PROJECTION GREATER THAN 72", THEN IT SHALL |
| | HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 15) SHEET A-2.1.3 & A-2.2.3 THERE SEEMS TO BE A |
| | DISCREPANCY BETWEEN THE 1 HR FIRE RATING AND THE 2HR |
| | FIRE RATING? 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 16) A-2.2.1 THIS SHEET INDICATES (3) AREAS WHERE ACCESS |
| | TO THE ROOF WILL BE THROUGH A ROOF HATCH. PLEASE NOTE, |
| | TO DATE THERE IS NO PRODUCT APPROVALS THAT COMPLY WITH |
| | THE FLORIDA STATE STATUTE RULE 9B-72 |
| | REQUIRING PRODUCT TESTING AND A THIRD PARTY QUALITY |
| | ASSURANCE PROGRAM. THIS ITEM WILL BE A PROVISO AND IF |
| | BY THE TIME A CERTIFICATE OF OCCUPANCY IS ASKED FOR THE |
| | MANUFACTURER OF THE ROOF HATCH WILL NEED TO HAVE |
| | RECEIVED EITHER A STATEWIDE APPROVAL, A ISSUED |
| | MIAMI-DADE NOTICE OF ACCEPTANCE(NOA) OR RECEIVED A |
| | LOCAL APPROVAL FROM THIS JURISDICTION. |
| | |
| | 17) M-2.2.0 THE BLOWER ROOM WHICH IS PART OF THE FIRE |
| | RATED ASSEMBLY INDICATES DUCT PENETRATION THROUGH THESE |
| | WALLS WITHOUT DAMPERS. 712.3.3 DUCTS AND AIR TRANSFER |
| | OPENINGS. |
| | |
| | 18) A-2.2.3 SPIRAL STAIR, STAIR# 201 TO CONTROL ROOM |
| | PLEASE SEE 1009.9.1(6) THE TURN OF THE STAIRWAY SHALL |
| | BE SUCH THAT DESCENDING USERS HAVE THE OUTER HANDRAIL |
| | AT THEIR RIGHT SIDE. PLEASE INDICATE COMPLIANCE. |
| | |
| | 19) A-3.1.1 PLANS INDICATE THE USE OF EFIS TRIM ABOVE |
| | 40'-0" PLEASE SEE 1406.2.2. ARCHITECTURAL TRIM THAT |
| | EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE |
| | SHALL BE CONSTRUCTED OF APPROVED NONCOMBUSTIBLE |
| | MATERIALS AND SHALL BE SECURED TO THE WALL WITH METAL |
| | OR OTHER APPROVED NONCOMBUSTIBLE BRACKETS. PLEASE |
| | PROVIDE THE ATTACHMENT DETAILS FOR THE EFIS OR EPS FOAM |
| | PRODUCTS WHERE THIS PRODUCT CAN BE USED BELOW 40'-" IN |
| | HEIGHT FROM GRADE. |
| | |
| | 20) A-6.1.3 DETAIL# 7INDICATES THE USE OF A HIP AND |
| | RIDGE BOARD BUT NO METHOD OF ATTACHMENT HAS BEEN |
| | INDICATED PLEASE SEE: |
| | 1507.3.7 ATTACHMENT. CLAY AND CONCRETE ROOF TILES SHALL |
| | BE FASTENED IN ACCORDANCE WITH SECTION 1609 OR IN |
| | ACCORDANCE WITH FRSA/TRI 07320 INSTALLATION MANUAL. |
| | |
| | 1507.3.8 APPLICATION. TILE SHALL BE APPLIED ACCORDING |
| | TO THE MANUFACTURER?S INSTALLATION INSTRUCTIONS OR |
| | RECOMMENDATIONS OF THE FRSA/TRI 07320. |
| | |
| | PLEASE INDICAT ON THE PLANS WHICH TYPE OF STEEL ANGLE |
| | PLACEMENT OF FASTENER AND SPACING OF BRACKET IN |
| | ACCORDANCE WITH FRSA/ TRI 07320. |
| | |
| | 21) SHEET A-6.1.4 VARIOUS DETAILS INDICATE THE USE OF |
| | 5/8 INCH CDX PLYWOOD ROOF DECKING, PLEASE SEE TABLE 601 |
| | FOOTNOTE (C) (2) WHERE FIRE RETARDANT TREATED PLYWOOD |
| | CAN AND CAN'T BE USED IN THE ROOF |
| | ASSEMBLIES. IF FIRE TREATED PLYWOOD IS TO BE USED, ALSO |
| | PROVIDE THE TYPE OF FASTENER AND TYPE OF METAL THE |
| | FASTENER WILL BE MADE FROM. |
| | |
| | 22) SHEET A-6.1.4 DETAIL "6" INDICATES THE USE OF UL |
| | SYSTEM P537, PLEASE REVIEW THIS SYSTEM VERSES WHAT IS |
| | SHOWN ON THE SHEET. THE PLANS AGAIN INDICATE THE 5/8 " |
| | CDX PLYWOOD ON THE ROOF DECK AS WELL AS BENEATH THE |
| | BOTTOM CORD OF THE TRUSS AS A BACKER BOARD. PLEASE |
| | REVIEW AND CORRECT. TABLE 601 FOOTNOTE (C)(2) AND |
| | SECTION 603. |
| | |
| | 23) A-6.1.6 DETAIL OR ELEVATION 1 INDICATES THE USE OF |
| | GILFORD FABRIC SCRIM STRETCHED AND STAPLED TO THE BACK |
| | OF FACED WOOD, PLEASE PROVIDE THE FLAME SPREAD RATING |
| | OF THIS FABRIC. |
| | |
| | 803.6.1 TEXTILE WALL COVERINGS. |
| | TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME |
| | SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE |
| | PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE |
| | COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1 |
| | OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE |
| | IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING |
| | SYSTEM, INCLUDING ADHESIVE. |
| | |
| | 803.6.1.1 METHOD A TEST PROTOCOL. |
| | DURING THE METHOD A PROTOCOL, FLAME SHALL NOT SPREAD TO |
| | THE CEILING DURING THE 40 KW EXPOSURE. DURING THE 150 |
| | KW EXPOSURE, THE TEXTILE WALL COVERING SHALL COMPLY |
| | WITH ALL OF THE FOLLOWING: |
| | 1. FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF THE |
| | SAMPLE ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM) |
| | WALL. |
| | 2. THE SPECIMEN SHALL NOT BURN TO THE OUTER EXTREMITY |
| | OF THE 2-FOOT-WIDE (610 MM) SAMPLES MOUNTED IN THE |
| | CORNER OF THE ROOM. |
| | 3. BURNING DROPLETS DEEMED CAPABLE OF IGNITING TEXTILE |
| | WALL COVERINGS OR THAT BURN FOR 30 SECONDS OR MORE |
| | SHALL NOT FORM. |
| | 4. FLASHOVER, AS DEFINED IN NFPA 265, SHALL NOT OCCUR. |
| | 5. THE MAXIMUM NET INSTANTANEOUS PEAK HEAT RELEASE |
| | RATE, DETERMINED BY SUBTRACTING THE BURNER OUTPUT FROM |
| | THE MAXIMUM HEAT RELEASE RATE, DOES NOT EXCEED 300 KW. |
| | |
| | |
| | 803.6.1.2 METHOD B TEST PROTOCOL. |
| | DURING THE METHOD B PROTOCOL, FLAMES SHALL NOT SPREAD |
| | TO THE CEILING AT ANY TIME DURING THE 40 KW EXPOSURE. |
| | DURING THE 150 KW EXPOSURE, THE TEXTILE WALL COVERING |
| | SHALL COMPLY WITH THE FOLLOWING: |
| | 1. FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES OF |
| | THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM) |
| | WALLS. |
| | 2. FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT |
| | OCCUR. |
| | |
| | 24) A-7.2.3 DETAIL# 2 INDICATES THE USE OF A 3 HOUR |
| | FUSED LINK DROP FIRE DOOR. PLEASE PROVIDE THE |
| | MANUFACTURERS SPEC FOR THIS PRODUCT. 715.3/ 106.1.2. |
| | |
| | |
| | 25) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 26) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | A) GLAZED OPENINGS, FIXED |
| | B) GLAZED OPENINGS, OPERABLE |
| | C) MULLIONS |
| | D) EXTERIOR GLAZED DOORS |
| | E) EXTERIOR HOLLOW METAL DOORS |
| | F) EXTERIOR ROLL UP DOORS |
| | G) ROOF ACCESS HATCHES |
| | H) PANEL WALL SYSTEMS : LOUVERS |
| | I) PANEL WALL SYSTEMS: EFIS WALL SYSTEMS ( NOT TRIM) J) |
| | ROOFING SYSTEMS BOTH FOR FLAT ROOF AND TILED SLOPED |
| | SYSTEMS |
| | |
| | 27) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 28) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 29) 1714.5.5 MULLIONS OCCURRING BETWEEN INDIVIDUAL |
| | WINDOW AND GLASS DOOR ASSEMBLIES. 1714.5.5.1 MULLIONS. |
| | MULLIONS, OTHER THAN MULLIONS WHICH ARE AN INTEGRAL |
| | PART OF A WINDOW OR GLASS DOOR ASSEMBLY TESTED AND |
| | LABELED IN ACCORDANCE WITH SECTION 1714.5.2.1 , SHALL |
| | BE TESTED BY AN APPROVED TESTING LABORATORY OR BE |
| | ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING |
| | PRACTICE. BOTH METHODS SHALL USE PERFORMANCE CRITERIA |
| | CITED IN SECTIONS 1714.5.5.2 , 1714.5.5.3 AND |
| | 1714.5.5.4 . |
| | |
| | 30) 1714.5.5.2 LOAD TRANSFER. MULLIONS SHALL BE |
| | DESIGNED TO TRANSFER THE DESIGN PRESSURE LOADS APPLIED |
| | BY THE WINDOW AND DOOR ASSEMBLIES TO THE ROUGH OPENING |
| | SUBSTRATE. |
| | |
| | 1714.5.5.4 STRUCTURAL SAFETY FACTOR. |
| | MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF |
| | ONE-AND-ONE-HALF TIMES THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW AND DOOR ASSEMBLIES TO BE |
| | SUPPORTED WITHOUT EXCEEDING THE APPROPRIATE MATERIAL |
| | STRESS LEVELS. IF TESTED BY AN APPROVED LABORATORY, THE |
| | ONE AND ONE-HALF TIMES THE DESIGN PRESSURE LOAD SHALL |
| | BE SUSTAINED FOR 10 SECONDS, AND THE PERMANENT |
| | DEFORMATION SHALL NOT EXCEED 0.4 PERCENT OF THE MULLION |
| | SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN PRESSURE |
| | LOAD IS REMOVED. |
| | |
| | 31) PLEASE REVIEW THE CRITERIA FOR FLAT ROOF PRODUCT |
| | APPROVAL SUBMITTALS, |
| | 106.1.1.2 FOR ROOFING ASSEMBLIES REQUIRED BY THIS CODE, |
| | THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE, |
| | AND DELINEATE THE TYPE OF ROOFING SYSTEMS, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| | FLAT ROOF: |
| | ____ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. |
| | |
| | ___ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM WILL |
| | BE INSTALLED. |
| | |
| | ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | _2&3__ . |
| | |
| | SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM |
| | HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED. |
| | |
| | ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT |
| | OR REGISTERED ROOF CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |