Plan Review Notes
Plan Review Notes For Permit 07110726
Permit Number 07110726
Review Stop P
Sequence Number 2
Notes
Date Text
2008-03-26 06:47:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A4 ADA UNISEX TOILET DETAIL. SHOW COMPLIANCE
 WITH THE FOLLOWING:
 ___FOR W/C
 A. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, NOT SHOWN ON PLANS.
 OK
 ___FOR LAV
 A. 11-4.19.5 FAUCETS
 ****RESPONSE NOTED, BUT FAUCET TYPE NOT INDICATED.
  
 NOTE: SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 3. ALL PME SHEETS IF THE ENGINEER IS PRACTICING THROUGH
 A DULY AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025.
 ****RESPONSE NOTED, BUT NO CERTIFICATE OF AUTHORIZATION
 FOR CAINE ENGINEERING INC. IS INDICATED ON THE STATE OF
 FLORIDA DBPR WEBSITE. THE NUMBER IN THE TITLE BLOCK IS
 NOT A CERTIFICATE OF AUTHORIZATION NUMBER.
  
 4. OK
 5. OK
  
 6. SHT P-1 SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE
 WATER PIPING SHOWING ALL PIPE SIZES, VALVES ETC.
 SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE.--WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI_WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
  
 7. OK
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]