Plan Review Notes
Plan Review Notes For Permit 07110726
Permit Number 07110726
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-05 19:26:012007-03-05 19:26:01
  
 ** DENIED2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE NUMBER WHICH WAS ADDED TO TITLE
 BLOCKS IN RESPONSE TO COMMENT WHICH REQUIRES THE
 CERTIFICATE OF AUTHORIZATION NUMBER ON PLANS IS NOT THE
 CA NUMBER. THIS MAY BE THE FLORIDA CORPORATE LICENSE
 NUMBER OR SOME OTHER NUMBER HOWEVER IS NOT THE
 ENGINEERING BUSINESS CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE SEE FS 471.023, FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 LIGHTING PERFORMANCE CALCULATIONS REQUIRED PER FBC
 13-415.2, 13-415.2.ABC.1.1.
 PLEASE SEE THE METHOD OF LIGHTING FIGURES SHOWN ON E-1
 DOES NOT INDICATE WHERE LEVELS ARE FROM
 PLEASE SEE THE LEVELS AS SUBMITTED EXCEED THE LEVELS
 PERMITTED IN EITHER TABLE B OR C IN SEVERAL LOCATIONS
 PLEASE SEE THE FIXTURE LEGEND ON E-1 AND E-2 DO NOT
 CORRELATE. THERE ARE SEVERAL FIXTURE/LUMINAIRE WATTAGES
 WHICH DO NOT MATCH. PLEASE COORDINATE.
  
 3) NOTE: PLEASE SEE THAT THE BUILDING AS DEFINED IS
 SHOWN LESS THEN 5K SQ FT HOWEVER LIGHTING CONTROL PER
 13-415.1.ABC.1.2 IS REQUIRED FOR SEPARATE SPACES.
 PLEASE SEE THAT CONFERENCE ROOM AND OTHER ROOMS AS
 LISTED IN THIS SECTION IS REQUIRED TO CONTAIN AUTOMATED
 CONTROL EVEN IF BUILDING IS UNDER 5K SQ FT. THIS IS A
 NEW COMMENT AS THIS WAS VERIFIED WITH THE FLORIDA
 BUILDING COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS
 SINCE LAST REVIEW.
  
 4) NOTE: PLEASE SEE KEY NOTE #2 ON SHEET E-0 WHICH
 MENTIONS TO SEE *EXXX* FOR REVISED LOAD CAPACITY OF NEW
 PANEL D1.
 THIS SEEMS TO BE A MISPRINT.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY
 REQUESTED NOT TO ATTACH SUPPORTING DOCUMENTS DOWN THE
 LEFT HAND SIDE OF PLANS YET THE PLANS CAME BACK IN WITH
 THESE DOCUMENTS ATTACHED TO PLANS ONCE AGAIN. THESE
 DOCUMENTS SHOULD BE PLACED IN SEPARATE BINDERS, FOLDERS
 ETC OF SOME KIND.
 THANK YOU ONCE AGAIN FOR YOUR ANTICIPATED COOPERATION.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-04 20:27:352008-03-04 20:27:35
  
 IN ELEC FOR REVIEW.