| 2008-03-05 19:26:01 | 2007-03-05 19:26:01 |
| | |
| | ** DENIED2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE THE NUMBER WHICH WAS ADDED TO TITLE |
| | BLOCKS IN RESPONSE TO COMMENT WHICH REQUIRES THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER ON PLANS IS NOT THE |
| | CA NUMBER. THIS MAY BE THE FLORIDA CORPORATE LICENSE |
| | NUMBER OR SOME OTHER NUMBER HOWEVER IS NOT THE |
| | ENGINEERING BUSINESS CERTIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | PLEASE SEE FS 471.023, FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| | LIGHTING PERFORMANCE CALCULATIONS REQUIRED PER FBC |
| | 13-415.2, 13-415.2.ABC.1.1. |
| | PLEASE SEE THE METHOD OF LIGHTING FIGURES SHOWN ON E-1 |
| | DOES NOT INDICATE WHERE LEVELS ARE FROM |
| | PLEASE SEE THE LEVELS AS SUBMITTED EXCEED THE LEVELS |
| | PERMITTED IN EITHER TABLE B OR C IN SEVERAL LOCATIONS |
| | PLEASE SEE THE FIXTURE LEGEND ON E-1 AND E-2 DO NOT |
| | CORRELATE. THERE ARE SEVERAL FIXTURE/LUMINAIRE WATTAGES |
| | WHICH DO NOT MATCH. PLEASE COORDINATE. |
| | |
| | 3) NOTE: PLEASE SEE THAT THE BUILDING AS DEFINED IS |
| | SHOWN LESS THEN 5K SQ FT HOWEVER LIGHTING CONTROL PER |
| | 13-415.1.ABC.1.2 IS REQUIRED FOR SEPARATE SPACES. |
| | PLEASE SEE THAT CONFERENCE ROOM AND OTHER ROOMS AS |
| | LISTED IN THIS SECTION IS REQUIRED TO CONTAIN AUTOMATED |
| | CONTROL EVEN IF BUILDING IS UNDER 5K SQ FT. THIS IS A |
| | NEW COMMENT AS THIS WAS VERIFIED WITH THE FLORIDA |
| | BUILDING COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS |
| | SINCE LAST REVIEW. |
| | |
| | 4) NOTE: PLEASE SEE KEY NOTE #2 ON SHEET E-0 WHICH |
| | MENTIONS TO SEE *EXXX* FOR REVISED LOAD CAPACITY OF NEW |
| | PANEL D1. |
| | THIS SEEMS TO BE A MISPRINT. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY |
| | REQUESTED NOT TO ATTACH SUPPORTING DOCUMENTS DOWN THE |
| | LEFT HAND SIDE OF PLANS YET THE PLANS CAME BACK IN WITH |
| | THESE DOCUMENTS ATTACHED TO PLANS ONCE AGAIN. THESE |
| | DOCUMENTS SHOULD BE PLACED IN SEPARATE BINDERS, FOLDERS |
| | ETC OF SOME KIND. |
| | THANK YOU ONCE AGAIN FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-03-04 20:27:35 | 2008-03-04 20:27:35 |
| | |
| | IN ELEC FOR REVIEW. |