| Date |
Text |
| 2007-12-15 11:14:27 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. RELATIVE CODES THAT THE PROJECT IS TO BE DESIGNED TO |
| | ARE THE FBC-2004 W/2007 REVISIONS. PLEASE INDICATE ON |
| | THE PLANS. |
| | |
| | 2. SHT A4 ADA UNISEX TOILET DETAIL. SHOW COMPLIANCE |
| | WITH THE FOLLOWING: |
| | ___FOR W/C |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE |
| | FIXTURE. FIG. 28. PLEASE SHOW ON DETAIL. |
| | ___FOR LAV |
| | A. 11-4.19.5 FAUCETS |
| | |
| | 3. ALL PME SHEETS IF THE ENGINEER IS PRACTICING THROUGH |
| | A DULY AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FS 471.025. |
| | |
| | 4. ALL PME SHEETS. A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME. THE SIGNATURE IS REQUIRED. IT APPEARS THAT |
| | INITIALS HAVE BEEN USED. IF THIS IS INDEED THE LEGAL |
| | SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED, |
| | DATED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE |
| | SHALL BE SUBMITTED FOR OUR RECORDS. FAC 61G15-23.002(1) |
| | & FS 471.025. |
| | |
| | 5. ALL PME SHEETS. THE SEAL USED IS NOT APPROVED. PER |
| | THE LETTER FROM THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS, AS OF JAN. 1 2006, (AFTER A 2 YEAR GRACE |
| | PERIOD), THE SEAL SHALL BE CHANGED FROM THE WORD |
| | "CERTIFICATE" TO THE WORD "LICENSE". PLEASE SEAL WITH |
| | THE NEW SEAL, AND MAKE SURE ALL INFORMATION REQUIRED ON |
| | THE EMBOSSED SEAL IS IMPRESSED ON EACH SHEET. |
| | |
| | 6. SHT P-1 SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE |
| | WATER PIPING SHOWING ALL PIPE SIZES, VALVES ETC. |
| | SECTION 106.3.5.1.3. |
| | |
| | 7. SHT P-1 SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE |
| | SANITARY PIPING SHOWING ALL PIPE SIZES, TRAPS, & VENTS. |
| | SECTION 106.3.5.1.3. |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |