2007-12-12 13:07:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. COVER SHEET INDICATES THERE SHOULD BE TWO MECHANICAL
 PAGES, M-1 AND M-2. HOWEVER, ONLY PAGE M-1 COULD BE
 FOUND IN PLANS. PLEASE CLARIFY AND/OR PROVIDE MISSING
 INFORMATION. FBC 106.1.1
  
 2. PG LS1 DECLARES THIS TO BE A LEVEL 2 ALTERATION. ALL
 RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL
 SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN
 ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL PER FBC, EB
 609.1. PROVIDE OUTSIDE AIR CALCULATIONS WHICH INCLUDE
 OCCUPANCY CLASSIFICATIONS OF SPACES, OCCUPANT LOADS OF
 SPACES AND OUTSIDE AIR REQUIRED FOR EACH SPACE AS
 INDICATED IN FBC, M TABLE 403.3.
  
 3. M-1: THERE ARE NO DUCT SIZES SHOWN ON PLANS. PROVIDE
 ALL DUCT SIZES TO SHOW A COMPLETE DESIGN OF THE DUCT
 SYSTEM. FBC, M 601.1 AND FBC 106.1.1.
  
 4. M-1: RETURN GRILL IN THE WAITING AREA DOES NOT HAVE
 ANY CORRESPONDING DUCTWORK SHOWN. SHOW HOW BALANCED
 RETURN IS TO BE ACHIEVED IN THIS AREA IN ACCORDANCE
 WITH FBC, M 601.4. ALSO, THERE ARE A FEW LOCATIONS
 WHERE THERE ARE MULTIPLE GRILLS SHOWN ON PLAN WITH ONLY
 SOME HAVING DUCTWORK ROUTED TO THEM. EXAMPLE: WAITING
 AREA SHOWS 4 OR 5 SUPPLY GRILLS WITH ONLY 2 OF THEM
 BEING DUCTED. PLEASE CLARIFY. FBC, M 603.1 AND FBC
 106.1.1
  
 5. M-1: PROVIDE INFORMATION OR EQUIPMENT SCHEDULE FOR
 TOILET EXHAUST FAN. EXHAUST RATE SHALL BE AS REQUIRED
 BY FBC, M TABLE 403.3. ALSO, SHOW HOW FAN IS TO BE
 CONTROLLED TO ASSURE ALL AIR SUPPLIED TO THIS ROOM IS
 EXHAUSTED IN ACCORDANCE WITH FBC, M 403.2.1(3).
  
 6. SHOW THE TYPE AND R-VALUE OF SUPPLY AND RETURN DUCT
 TO BE USED. AIR DISTRIBUTION SYSTEM COMPONENTS ARE TO
 HAVE MINIMUM INSULATION LEVELS IN ACCORDANCE WITH FBC
 TABLE 13-410.1.ABC.2.2. NO INFORMATION COULD BE FOUND
 ON PLANS INDICATING THE TYPE OR R-VALUE OF ROOF
 INSULATION IN THE EXISTING BUILDING. THIS INFORMATION
 IS REQUIRED TO DETERMINE THE REQUIRED MINIMUM R-VALUE
 OF INSULATION FOR THE AIR DISTRIBUTION SYSTEM.
 NOTE: IF THIS IS AN ATTIC WITH CEILING INSULATION, ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING PANELS. AT LEAST ONE
 PORTION OF THE WORK AREA IS SHOWN WITH A DROPPED GRID
 CEILING AREA. INSULATION MAY NOT BE INSTALLED ON THIS
 CEILING IN ACCORDANCE WITH FBC 13-404.1.ABC.1.
  
 7. PLEASE SEE ELECTRICAL COMMENTS REGARDING THE
 SIGNATURE, SEAL AND MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE DESIGNER OF RECORD. MAKE
 NECESSARY CORRECTIONS PRIOR TO RESUBMITTAL.
  