Plan Review Notes
Plan Review Notes For Permit 07110726
Permit Number 07110726
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-12 08:41:01 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE RELEVANT CODES/DESIGN FOR THIS
 PROJECT IS REQUIRED TO BE STATED ON PLANS.
 PLEASE KNOW THE CODES STATE-WIDE CHANGED ON DECEMBER
 8TH, 2006. PLEASE ALSO KNOW THERE WERE ALSO REVISIONS
 TO THE FLORIDA BUILDING CODE SINCE THAT DATE ALSO.
 PLEASE SEE THE FOLLOWING IS REQUIRED TO BE STATED ON
 PLANS INCLUDING ELECTRICALSHEETS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE THERE ARE SEVERAL CODES SECTIONS WHICH
 ARE REFLECTED ON THE ELECTRICAL PANEL SCHEDULES FOR
 LOAD CALCULATIONS. PLEASE SEE THAT THESE ARE NOT FROM
 THE CURRENT CODE OF THE 2005 NEC.
 THESE ARE FROM THE PREVIOUS CODE. PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ON ALL MEP PLANS
 ARE MISSING THE CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED PER FLORIDA STATUES 471.023. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES
 THIS NUMBER TO BE LOCATED ON TITLE BLOCKS.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE THE SEAL WHICH IS IN USE ON THE MEP
 PLANS IS NO LONGER VALID WITHIN THE STATE OF FLORIDA.
 PLEASE SEE RULING 61G15-23.001 WHICH WAS PASSED IN
 FEBRUARY 2004. THIS RULE REQUIRED ALL ENGINEERS WITH
 THE WORDING OF *CERTIFICATE* IN SAID SEAL TO HAVE SEALS
 CHANGED TO THE WORDING OF *LICENSE*. THERE WAS AND
 EXTENSION GRANTED TO DECEMBER 31ST, 2005 HOWEVER ALL
 PLANS AFTER THIS DATE MUST HAVE THE NEW SEAL.
 PLEASE OBTAIN NEW SEAL.
 THE SEAL IS NO LONGER ACCEPTABLE ON PLANS IN THE STATE
 AS THIS RULE WAS CHANGED ALMOST THREE YEARS AGO.
 ** PLEASE KNOW WHEN SEALING PLANS PLEASE BE SURE THE
 RAISED SEAL IS CLEAR AND VISIBLE WITH ALL INFORMATION
 ON SAID SEAL. THE SEAL IS VERY FAINT AND NOT EASILY
 READ. FS471.025
  
 4) NOTE: PLEASE SEE THE PLANS APPEARS TO BE SIGNED WITH
 *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE OF
 THE DESIGNER PLEASE PROVIDE A SIGNED, DATED, SEALED AND
 NOTARIZED LETTER FOR SIGNATURE VERIFICATION. THIS WILL
 BE PLACED IN SIGNATURE FILE FOR ANY FUTURE REFERENCES.
 PLEASE BE SURE THE NOTARIZED LETTER CONTAINS THE
 INFORMATION AS REQUIRED PER FS 117.05.
 FS 471.025
  
 5) NOTE: PLEASE SEE THE PLANS NOTE IN TWO LOCATIONS
 THAT THE CONTRACTOR IS RESPONSIBLE TO VERIFY LOAD ON
 EXISTING EQUIPMENT AND ADJUST CONDUCTORS, BREAKER SIZES
 ETC AS NEEDED.
 PLEASE KNOW THE RESPONSIBILITY IS THAT OF THE ENGINEER
 UNDER RESPONSIBILITY OF DESIGNS UNDER FAC 61G15-33.003
 AND 61G15-33.003.
 ALL LOADS ON EXISTING EQUIPMENT SHALL BE VERIFIED AT
 THIS TIME AS THE CODE REQUIRES THIS AS A MINIMUM.
 PLEASE SEE 220.87, 220.
 PLEASE SUBMIT LOAD ON THE EXISTING MDP WITH NEW AND
 EXISTING LOADS BEING ADDED.
 PLEASE MAKE ANY CHANGES TO EQUIPMENT, CONDUCTORS,
 BREAKERS ETC AS NEEDED.
  
 6) NOTE: PLEASE SEE THE LOCATION OF PANEL *D* AS NOTED
 ON PANEL SCHEDULE MENTIONS THIS PANEL IS LOCATED IN THE
 ELECTRICAL ROOM, HOWEVER THE PANEL ON PLANS IS SHOWN IN
 THE CONFERENCE ROOM.
 PLEASE VERIFY THIS LOCATION.
 PLEASE ALSO VERIFY THE LOCATION OF THE NEW PANEL AS THE
 PLANS APPEAR TO SHOW WHAT APPEARS TO BE SOME SORT OF
 BOX IN FRONT OF PANEL ON ONE SIDE.
 PLEASE SEE 110.26, 240.24 ETC FOR LOCATION OF PANELS
 AND MINIMUM CLEARANCES.
  
 7) NOTE: PLEASE CLARIFY THE PANEL SIZE AND BREAKER AS
 SHOWN. PLEASE SEE FOR EXAMPLE: THE PANEL IS BEING SHOWN
 AS 100AMP MCB (MAIN CIRCUIT BREAKER) ON SCHEDULE,
 HOWEVER RISER SHOWS THIS AS A 60AMP MLO (MAIN LUG
 ONLY).
 WHICH ONE IS IT?
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 8) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13 AND PROVIDE NOTES ON
 PLANS PER 13-413.1.ABC.2.1 AND .2.2.
  
 10) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2 AND
 PROVIDE LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SEE INTERIOR LIGHTING ALLOWANCES ALSO PER
 13-415.2.ABC .1.2 ETC.
 PLEASE BE SURE ALL CALCULATIONS CORRELATE WITH THE
 FIXTURE LEGEND AS SHOWN.
  
 11) NOTE: WHEN SUBMITTING SUPPORTING DOCUMENTS SUCH AS
 CALCULATIONS, PRODUCT APPROVALS ETC PLEASE DO NOT
 ATTACH DOWN THE LEFT HAND SIDE OF THE PLANS.
 THIS WILL HELP IN PROCESSING OF PLANS. YOUR COOPERATION
 IS APPRECIATED.
 FBC ADMIN 106.1
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-12 07:31:05 
 IN ELEC FOR REVIEW