| Date |
Text |
| 2007-12-12 08:41:01 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE RELEVANT CODES/DESIGN FOR THIS |
| | PROJECT IS REQUIRED TO BE STATED ON PLANS. |
| | PLEASE KNOW THE CODES STATE-WIDE CHANGED ON DECEMBER |
| | 8TH, 2006. PLEASE ALSO KNOW THERE WERE ALSO REVISIONS |
| | TO THE FLORIDA BUILDING CODE SINCE THAT DATE ALSO. |
| | PLEASE SEE THE FOLLOWING IS REQUIRED TO BE STATED ON |
| | PLANS INCLUDING ELECTRICALSHEETS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL CODES SECTIONS WHICH |
| | ARE REFLECTED ON THE ELECTRICAL PANEL SCHEDULES FOR |
| | LOAD CALCULATIONS. PLEASE SEE THAT THESE ARE NOT FROM |
| | THE CURRENT CODE OF THE 2005 NEC. |
| | THESE ARE FROM THE PREVIOUS CODE. PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCKS ON ALL MEP PLANS |
| | ARE MISSING THE CERTIFICATE OF AUTHORIZATION NUMBER AS |
| | REQUIRED PER FLORIDA STATUES 471.023. PLEASE SEE |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES |
| | THIS NUMBER TO BE LOCATED ON TITLE BLOCKS. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE THE SEAL WHICH IS IN USE ON THE MEP |
| | PLANS IS NO LONGER VALID WITHIN THE STATE OF FLORIDA. |
| | PLEASE SEE RULING 61G15-23.001 WHICH WAS PASSED IN |
| | FEBRUARY 2004. THIS RULE REQUIRED ALL ENGINEERS WITH |
| | THE WORDING OF *CERTIFICATE* IN SAID SEAL TO HAVE SEALS |
| | CHANGED TO THE WORDING OF *LICENSE*. THERE WAS AND |
| | EXTENSION GRANTED TO DECEMBER 31ST, 2005 HOWEVER ALL |
| | PLANS AFTER THIS DATE MUST HAVE THE NEW SEAL. |
| | PLEASE OBTAIN NEW SEAL. |
| | THE SEAL IS NO LONGER ACCEPTABLE ON PLANS IN THE STATE |
| | AS THIS RULE WAS CHANGED ALMOST THREE YEARS AGO. |
| | ** PLEASE KNOW WHEN SEALING PLANS PLEASE BE SURE THE |
| | RAISED SEAL IS CLEAR AND VISIBLE WITH ALL INFORMATION |
| | ON SAID SEAL. THE SEAL IS VERY FAINT AND NOT EASILY |
| | READ. FS471.025 |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS APPEARS TO BE SIGNED WITH |
| | *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE OF |
| | THE DESIGNER PLEASE PROVIDE A SIGNED, DATED, SEALED AND |
| | NOTARIZED LETTER FOR SIGNATURE VERIFICATION. THIS WILL |
| | BE PLACED IN SIGNATURE FILE FOR ANY FUTURE REFERENCES. |
| | PLEASE BE SURE THE NOTARIZED LETTER CONTAINS THE |
| | INFORMATION AS REQUIRED PER FS 117.05. |
| | FS 471.025 |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS NOTE IN TWO LOCATIONS |
| | THAT THE CONTRACTOR IS RESPONSIBLE TO VERIFY LOAD ON |
| | EXISTING EQUIPMENT AND ADJUST CONDUCTORS, BREAKER SIZES |
| | ETC AS NEEDED. |
| | PLEASE KNOW THE RESPONSIBILITY IS THAT OF THE ENGINEER |
| | UNDER RESPONSIBILITY OF DESIGNS UNDER FAC 61G15-33.003 |
| | AND 61G15-33.003. |
| | ALL LOADS ON EXISTING EQUIPMENT SHALL BE VERIFIED AT |
| | THIS TIME AS THE CODE REQUIRES THIS AS A MINIMUM. |
| | PLEASE SEE 220.87, 220. |
| | PLEASE SUBMIT LOAD ON THE EXISTING MDP WITH NEW AND |
| | EXISTING LOADS BEING ADDED. |
| | PLEASE MAKE ANY CHANGES TO EQUIPMENT, CONDUCTORS, |
| | BREAKERS ETC AS NEEDED. |
| | |
| | 6) NOTE: PLEASE SEE THE LOCATION OF PANEL *D* AS NOTED |
| | ON PANEL SCHEDULE MENTIONS THIS PANEL IS LOCATED IN THE |
| | ELECTRICAL ROOM, HOWEVER THE PANEL ON PLANS IS SHOWN IN |
| | THE CONFERENCE ROOM. |
| | PLEASE VERIFY THIS LOCATION. |
| | PLEASE ALSO VERIFY THE LOCATION OF THE NEW PANEL AS THE |
| | PLANS APPEAR TO SHOW WHAT APPEARS TO BE SOME SORT OF |
| | BOX IN FRONT OF PANEL ON ONE SIDE. |
| | PLEASE SEE 110.26, 240.24 ETC FOR LOCATION OF PANELS |
| | AND MINIMUM CLEARANCES. |
| | |
| | 7) NOTE: PLEASE CLARIFY THE PANEL SIZE AND BREAKER AS |
| | SHOWN. PLEASE SEE FOR EXAMPLE: THE PANEL IS BEING SHOWN |
| | AS 100AMP MCB (MAIN CIRCUIT BREAKER) ON SCHEDULE, |
| | HOWEVER RISER SHOWS THIS AS A 60AMP MLO (MAIN LUG |
| | ONLY). |
| | WHICH ONE IS IT? |
| | FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION. |
| | |
| | 8) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 |
| | |
| | 9) NOTE: PLEASE SEE FBC CHAPTER 13 AND PROVIDE NOTES ON |
| | PLANS PER 13-413.1.ABC.2.1 AND .2.2. |
| | |
| | 10) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2 AND |
| | PROVIDE LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE SEE INTERIOR LIGHTING ALLOWANCES ALSO PER |
| | 13-415.2.ABC .1.2 ETC. |
| | PLEASE BE SURE ALL CALCULATIONS CORRELATE WITH THE |
| | FIXTURE LEGEND AS SHOWN. |
| | |
| | 11) NOTE: WHEN SUBMITTING SUPPORTING DOCUMENTS SUCH AS |
| | CALCULATIONS, PRODUCT APPROVALS ETC PLEASE DO NOT |
| | ATTACH DOWN THE LEFT HAND SIDE OF THE PLANS. |
| | THIS WILL HELP IN PROCESSING OF PLANS. YOUR COOPERATION |
| | IS APPRECIATED. |
| | FBC ADMIN 106.1 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-12-12 07:31:05 | |
| | IN ELEC FOR REVIEW |