Plan Review Notes
Plan Review Notes For Permit 07110724
Permit Number 07110724
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-05 15:13:29** DENIED**
  
 1) NOTE: PLEASE SUBMIT THE PANEL SCHEDULE AND/OR PANEL
 WHERE NEW CIRCUITS ARE BEING FED FROM.
 PLEASE LIST AND SHOW ANY INCREASE OF LOADS ON THE
 PANEL. 220.12,220.14,220.44,220.42 ETC
 PLEASE SUBMIT.
 408.4, 240.4, 310.16 ETC
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS FOR ANY
 NEW CONTROLS BEING INSTALLED OR REPLACED.
 13-415.1.ABC.1.1, .1.2.
  
 3) NOTE: PLEASE PROVIDE LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AREAS PER 13-415.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  