2007-12-04 08:08:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 11A STATES RETURN AIR DUCTS
 ARE IN A CONDITIONED SPACE AND THE AIR HANDLER IN
 INSTALLED IN THE INTERIOR, THE MECHANICAL PLANS SHOW
 THE RETURN AIR DUCTS AND AIR HANDLER ARE IN THE ATTIC.
 PLEASE CORRECT ENERGY CAL'S. SEE 2004 FBC
 13-610.2.A.1.
  
 2) ENERGY CALCULATIONS LINE 15 IS TAKING MULTIZONE
 CREDIT, AS THE ENERGY CAL'S. ARE FOR THE ADDITION ONLY
 OTHER PARTS OF THE BUILDING MAY NOT BE INCLUDED. YOU
 MAY DO THE ENERGY CAL'S. FOR THE WHOLE BUILDING OR
 REMOVE THE MZ-C. SEE 2004 FBC 13-607.2.A.3.2.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 4) THE JOB ADDRESS NEEDS TO BE ON THE MECHANICAL PLAN,
 SEE 2004 WPB AMEND. 106.1.3.
  
 5) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]