Plan Review Notes
Plan Review Notes For Permit 07110645
Permit Number 07110645
Review Stop B
Sequence Number 2
Notes
Date Text
2008-02-07 18:08:04PROJECT: 721 38TH STREET/ #07110645
  
 PROJECT DETAIL: CHANGE OF OCCUPANCY (R-3 TO R-4)
  
 CODE REVIEW:
  
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH AMENDMENTS, CHAPTER 1, 2004
 EDITION
  
  
 STATUS: FAIL
  
 COMMENTS:
  
 1) PLEASE PROVIDE CLARIFICATION OF THE PROPSED SCOPE OF
 WORK: INDICATE ARES OF EXISTING CONSTRUCTION AND NEW
 CONSTRUCTION.
  
 2) 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS AS PER THE
 FOLLOWING:
  
 FEBC
 512.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 4) PLEASE PROVIDE WINDOW AND DOOR PRODUCT APPROVALS X 2
 COPIES FOR NEW WINDOW/DOOR INSTALLATION.
  
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR NEW ROOF
 COVERING.
  
 6) PLEASE INDICATE THE DESIGN PRESSURES FOR THE
 OFFICE/BATHROOM DOORS AND OFFICE WINDOW.
  
 7) PLEASE INDICATE THE EXISTING BEDROOM WINDOW
 DIMENSIONS. THE WINDOWS SHALL COMPLY WITH FEBC, SECTION
 812.4.1.1:
  
 812.4.1.1MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY.
 WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A HIGHER
 HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 812.4.1, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 EXCEPTIONS:
 1. STAIRWAYS SHALL BE ENCLOSED IN COMPLIANCE WITH THE
 APPLICABLE PROVISIONS OF SECTION 703.1. 2. EXISTING
 STAIRWAYS INCLUDING HANDRAILS AND GUARDS COMPLYING WITH
 THE REQUIREMENTS OF CHAPTER 7 SHALL BE PERMITTED FOR
 CONTINUED USE SUBJECT TO APPROVAL OF THE CODE
 OFFICIAL.
 3. ANY STAIRWAY REPLACING AN EXISTING STAIRWAY WITHIN A
 SPACE WHERE, BECAUSE OF EXISTING CONSTRUCTION, THE
 PITCH OR SLOPE CANNOT BE REDUCED, SHALL BE PERMITTED
 FOR CONTINUED USE SUBJECT TO APPROVAL OF THE BUILDING
 CODE OFFICIAL.
 4. WHERE AN EXISTING CORRIDOR IS REQUIRED TO BE FIRE
 RATED, EQUIVALENCY CAN BE ACHIEVED BY EITHER
 SPRINKLERING THE BUILDING OR USING EQUIVALENCY AS PER
 NFPA 914 OR CHAPTER 7 OF THE FLORIDA BUILDING CODE,
 BUILDING FOR FIRE RESISTANCE. ALSO, SEE SECTION 1001.2
 OF THE FLORIDA BUILDING CODE, BUILDING. 5. EXISTING
 CORRIDOR DOORWAYS, TRANSOMS, AND OTHER CORRIDOR
 OPENINGS SHALL COMPLY WITH THE REQUIREMENTS IN SECTIONS
 605.5.1, 605.5.2, AND 605.5.3. 6. EXISTING DEAD-END
 CORRIDORS SHALL COMPLY WITH THE REQUIREMENTS IN SECTION
 605.6.
 7. WHERE EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 REQUIRED, AN EXISTING OPERABLE WINDOW WITH CLEAR
 OPENING AREA NO LESS THAN 4 SQUARE FEET (0.38 M2) AND
 WITH MINIMUM OPENING HEIGHT AND WIDTH OF 22 INCHES (559
 MM) AND 20 INCHES (508 MM), RESPECTIVELY, WITH MAXIMUM
 SILL HEIGHT AT 44 INCHES (1118 MM) ABOVE THE FLOOR OR
 APPROVED PERMANENT ELEVATED AREA, SHALL BE ACCEPTED AS
 AN EMERGENCY ESCAPE AND RESCUE OPENING.
  
 8) PLEASE INDICATE THE PROPOSED OCCUPANT LOAD:
  
 FBC 1004.1DESIGN OCCUPANT LOAD.
 IN DETERMINING MEANS OF EGRESS REQUIREMENTS, THE NUMBER
 OF OCCUPANTS FOR WHOM MEANS OF EGRESS FACILITIES SHALL
 BE PROVIDED SHALL BE ESTABLISHED BY THE LARGEST NUMBER
 COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH
 1004.1.3.
  
 9) PLEASE SHOW ACCESSIBLE ROUTE, PARKING, RAMPS AND
 ACCESSIBLE BATHROOMS AND INDICATE DIMENSIONS:
  
 812.5ACCESSIBILITY.
 EXISTING BUILDINGS OR PORTIONS THEREOF THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG