| Plan Review Notes For Permit 07110645 |
| Permit Number |
07110645 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-02-11 14:43:29 | DENIED; | | | 1. LIST ON PLANS THE NUMBER OF RESIDENTS THAT WILL LIVE | | | IN HOUSE. PER FBC-2004 EXISTING BUILDING CODE SECTION | | | 810. | | | 2. MINIMUM PLUMBING FIXTURES REQUIRES A DRINKING | | | FOUNTAIN AND A SERVICE SINK. SEE FBC PLUMBING TABLE | | | 403.1. | | | 3. BATHROOMS MUST BE HANDICAP ACCESSIBLE PER EXISTING | | | BUILDING CODE SECTION 812.5. SHOW TURNING RADIUS IN | | | EACH BATHROOM, AND DETAILS OF W/C, LAVATORY, AND SHOWER | | | OR TUB PER FBC BUILDING CHAPTER 11, SECTIONS 11-4.15 | | | DRINKING FOUNTAIN, 11-4.16 TOILET, 11-4.19 LAVATORYS | | | AND MIRRORS, AND 11-4.21 SHOWERS. | | | 4. A BACKFLOW WILL ALSO BE REQUIRED AT THE WATER METER | | | PER UTILITY DEPARTMENT ORDINANCE # 2853-95. PLEASE ADD | | | NOTE TO PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|